21.11.2012 Views

Design overhead distribution systems

Design overhead distribution systems

Design overhead distribution systems

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Electrical, Electronics<br />

Engineering Department<br />

<strong>Design</strong> <strong>overhead</strong><br />

<strong>distribution</strong> <strong>systems</strong><br />

UETTDRDS05B<br />

(Vol 1 of 2)<br />

Version No 1 2 3 4 5<br />

Date 10/2005 06/2009 05/2010<br />

Refer to: DMcR DK DK<br />

Chisholm Institute of TAFE<br />

Dandenong Campus<br />

Stud Road<br />

DANDENONG 3175<br />

Tel: +61 3 9212 5200<br />

Fax: +61 3 9212 5232


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

This page intentionally left blank<br />

2


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Contents<br />

Electric power transmission ....................................................................................................... 5<br />

Overhead transmission .......................................................................................................... 7<br />

Structures .............................................................................................................................. 8<br />

Conductors ............................................................................................................................ 9<br />

Train power .......................................................................................................................... 10<br />

Further applications.............................................................................................................. 10<br />

Usage of area under <strong>overhead</strong> power lines .......................................................................... 11<br />

Electricity Power Supply Systems ............................................................................................ 12<br />

Distribution Systems and Voltage Levels ............................................................................. 12<br />

Types of <strong>distribution</strong> feeder <strong>systems</strong> .................................................................................... 14<br />

Revision exercise 1 ................................................................................................................. 17<br />

Overhead and Underground Power Systems ....................................................................... 18<br />

Overhead Insulated Conductors ........................................................................................... 19<br />

Revision exercise 2 ................................................................................................................. 19<br />

Three Phase, Single Phase and Single Wire Earth Return Systems ........................................ 20<br />

Revision Exercise 3 ................................................................................................................. 26<br />

Revision Exercise 4 ................................................................................................................. 28<br />

Revision exercise 5 ................................................................................................................. 31<br />

Terminology ......................................................................................................................... 33<br />

Revision exercise 6 ................................................................................................................. 34<br />

Revision exercise 7 ................................................................................................................. 39<br />

Equipment used in the control of voltage ................................................................................. 40<br />

Types of voltage regulators .................................................................................................. 42<br />

Revision exercise 8 ................................................................................................................. 47<br />

Revision exercise 9 ................................................................................................................. 51<br />

Wires and Cables .................................................................................................................... 53<br />

3


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

MODULE TITLE <strong>Design</strong> <strong>overhead</strong> <strong>distribution</strong> <strong>systems</strong><br />

Nominal Duration 40 hours<br />

Module Code or Number UETTDRDS05A<br />

T2.2.2 Transmission, <strong>distribution</strong> and rail power <strong>systems</strong><br />

T2.2.4 Powerline <strong>distribution</strong> installation<br />

T2.4.6 High voltage SWER system<br />

List of essential resources<br />

- Voltage regulation relay - typical working sample<br />

- Line drop compensator<br />

- Phantom line circuit - simulating a typical transmission or <strong>distribution</strong> feeder<br />

- Sample VT and CT<br />

- Local <strong>distribution</strong> system diagrams - with fault levels indicated<br />

- Low voltage AC supply<br />

- Extra low voltage AC supply<br />

- Low voltage DC supply<br />

Items such as the voltage regulation relay, line drop compensator and VT may be difficult to<br />

obtain, student exposure to this equipment may be obtained with the aid of industrial visits.<br />

4


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Electric power transmission<br />

Electric power transmission is the bulk transfer of electrical energy, a process in the delivery of<br />

electricity to consumers.<br />

A power transmission network typically connects power plants to multiple substations near a<br />

populated area.<br />

The wiring from substations to customers is referred to as electricity <strong>distribution</strong>, following the<br />

historic business model separating the wholesale electricity transmission business from<br />

distributors who deliver the electricity to the homes.<br />

Electric power transmission allows distant energy sources (such as hydroelectric power plants) to<br />

be connected to consumers in population centres, and may allow exploitation of low-grade fuel<br />

resources such as coal that would otherwise be too costly to transport to generating facilities.<br />

5


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Transmission lines<br />

Usually transmission lines use three phase alternating current (AC). Single phase AC current is<br />

sometimes used in a railway electrification system. High-voltage direct current <strong>systems</strong> are used<br />

for long distance transmission, or some undersea cables, or for connecting two different ac<br />

networks.<br />

Electricity is transmitted at high voltages (110 kV or above) to reduce the energy lost in<br />

transmission.<br />

Power is usually transmitted as alternating current through <strong>overhead</strong> power lines. Underground<br />

power transmission is used only in densely populated areas because of its higher cost of<br />

installation and maintenance when compared with <strong>overhead</strong> wires, and the difficulty of voltage<br />

control on long cables.<br />

A power transmission network is referred to as a "grid". Multiple redundant lines between points<br />

on the network are provided so that power can be routed from any power plant to any load center,<br />

through a variety of routes, based on the economics of the transmission path and the cost of<br />

power.<br />

Much analysis is done by transmission companies to determine the maximum reliable capacity of<br />

each line, which, due to system stability considerations, may be less than the physical or thermal<br />

limit of the line.<br />

Deregulation of electricity companies in many countries has led to renewed interest in reliable<br />

economic design of transmission networks.<br />

A power station (also referred to as a generating station, power plant, or powerhouse) is an<br />

industrial facility for the generation of electric power.<br />

Power plant is also used to refer to the engine in ships, aircraft and other large vehicles. Some<br />

prefer to use the term energy centre because it more accurately describes what the plants do,<br />

which is the conversion of other forms of energy, like chemical energy, gravitational potential<br />

energy or heat energy into electrical energy. However, power plant is the most common term in<br />

the U.S., while elsewhere power station and power plant are both widely used, power station<br />

prevailing in many Commonwealth countries and especially in the United Kingdom.<br />

At the center of nearly all power stations is a generator, a rotating machine that converts<br />

mechanical energy into electrical energy by creating relative motion between a magnetic field and<br />

a conductor.<br />

The energy source harnessed to turn the generator varies widely. It depends chiefly on which<br />

fuels are easily available and on the types of technology that the<br />

power company has access to.<br />

Hydroelectric Station Steam Electric Station<br />

6


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Overhead transmission<br />

Overhead conductors are not covered by insulation.<br />

The conductor material is nearly always an aluminium alloy, made into several strands and<br />

possibly reinforced with steel strands.<br />

Copper was sometimes used for <strong>overhead</strong> transmission but aluminium is lower in weight for<br />

equivalent performance, and much lower in cost.<br />

Overhead conductors are a commodity supplied by several companies worldwide. Improved<br />

conductor material and shapes are regularly used to allow increased capacity and modernize<br />

transmission circuits.<br />

Conductor sizes range from 12 mm² (#6 American wire gauge) to 750 mm² (1,590,000 circular<br />

mils area), with varying resistance and current-carrying capacity.<br />

Thicker wires would lead to a relatively small increase in capacity due to the skin effect, that<br />

causes most of the current to flow close to the surface of the wire.<br />

Today, transmission-level voltages are usually considered to be 110 kV and above.<br />

Lower voltages such as 66 kV and 33 kV are usually considered sub-transmission voltages but<br />

are occasionally used on long lines with light loads.<br />

Voltages less than 33 kV are usually used for <strong>distribution</strong>.<br />

Voltages above 230 kV are considered extra high voltage and require different designs compared<br />

to equipment used at lower voltages.<br />

Since <strong>overhead</strong> transmission lines are uninsulated, design of these lines requires minimum<br />

clearances to be observed to maintain safety.<br />

Adverse weather conditions of high wind and low temperatures can lead to power outages: wind<br />

speeds as low as 23 knots (43 km/h) can permit conductors to encroach operating clearances,<br />

resulting in a flashover and loss of supply.<br />

Oscillatory motion of the physical line can be termed gallop or flutter depending on the frequency<br />

and amplitude of oscillation.<br />

An <strong>overhead</strong> power line is an electric power transmission line suspended by towers or poles.<br />

Since most of the insulation is provided by air, <strong>overhead</strong> power lines are generally the lowest-cost<br />

method of transmission for large quantities of electric power.<br />

Towers for support of the lines are made of wood (as-grown or laminated), steel (either lattice<br />

structures or tubular poles), concrete, aluminum, and occasionally reinforced plastics. The bare<br />

wire conductors on the line are generally made of aluminum (either plain or reinforced with steel<br />

or sometimes composite materials), though some copper wires are used in medium-voltage<br />

<strong>distribution</strong> and low-voltage connections to customer premises.<br />

The invention of the strain insulator was a critical factor in allowing higher voltages to be used. At<br />

the end of the 19th century, the limited electrical strength of telegraph-style pin insulators limited<br />

the voltage to no more than 69,000 volts.<br />

Today <strong>overhead</strong> lines are routinely operated at voltages exceeding 765,000 volts between<br />

conductors, with even higher voltages possible in some cases.<br />

Overhead power transmission lines are classified in the electrical power industry by the range of<br />

voltages:<br />

Low voltage – less than 1000 volts, used for connection between a residential or small<br />

commercial customer and the utility.<br />

Medium Voltage (Distribution) – between 1000 volts (1 kV) and to about 33 kV, used for<br />

<strong>distribution</strong> in urban and rural areas.<br />

High Voltage (Subtransmission if 33-115kV and transmission if 115kV+) – between 33 kV and<br />

about 230 kV, used for sub-transmission and transmission of bulk quantities of electric power and<br />

connection to very large consumers.<br />

7


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Extra High Voltage (Transmission) – over 230 kV, up to about 800 kV, used for long distance,<br />

very high power transmission.<br />

Ultra High Voltage – higher than 800 kV.<br />

Lines classified as "High voltage" are quite hazardous. Direct contact with (touching) energized<br />

conductors still present a risk of electrocution.<br />

A major goal of <strong>overhead</strong> power line design is to maintain adequate clearance between energized<br />

conductors and the ground so as to prevent dangerous contact with the line.<br />

This is extremely dependent on the voltage the line is running at.<br />

Structures<br />

Structures for <strong>overhead</strong> lines take a variety of shapes depending on the type of line. Structures<br />

may be as simple as wood poles directly set in the earth, carrying one or more cross-arm beams<br />

to support conductors, or "armless" construction with conductors supported on insulators attached<br />

to the side of the pole.<br />

Tubular steel poles are typically used in urban areas. High-voltage lines are often carried on<br />

lattice-type steel towers or pylons. For remote areas, aluminium towers may be placed by<br />

helicopters.<br />

Concrete poles have also been used. Poles made of reinforced plastics are also available, but<br />

their high cost restricts application.<br />

Each structure must be designed for the loads imposed on it by the conductors.<br />

A large transmission line project may have several types of towers, with "tangent" ("suspension"<br />

or "line" towers, UK) towers intended for most positions and more heavily constructed towers<br />

used for turning the line through an angle, dead-ending (terminating) a line, or for important river<br />

or road crossings.<br />

Depending on the design criteria for a particular line, semi-flexible type structures may rely on the<br />

weight of the conductors to be balanced on both sides of each tower.<br />

More rigid structures may be intended to remain standing even if one or more conductors is<br />

broken.<br />

Such structures may be installed at intervals in power lines to limit the scale of cascading tower<br />

failures.<br />

Foundations for tower structures may be large and costly, particularly if the ground conditions are<br />

poor, such as in wetlands.<br />

Each structure may be considerably strengthened by the use of guy wires to resist some of the<br />

forces due to the conductors.<br />

Power lines and supporting structures can be a form of visual pollution. In some cases the lines<br />

are buried to avoid this, but this is more expensive and therefore not usual.<br />

Insulators<br />

Insulators must support the conductors and withstand both the normal operating voltage and<br />

surges due to switching and lightning. Insulators are broadly classified as either pin-type, which<br />

support the conductor above the structure, or suspension type, where the conductor hangs below<br />

the structure. Up to about 33 kV (69 kV in North America) both types are commonly used.<br />

At higher voltages only suspension-type insulators are common for <strong>overhead</strong> conductors.<br />

Insulators are usually made of wet-process porcelain or toughened glass, with increasing use of<br />

glass-reinforced polymer insulators.<br />

Suspension insulators are made of multiple units, with the number of unit insulator disks<br />

increasing at higher voltages.<br />

The number of disks is chosen based on line voltage, lightning withstand requirement, altitude,<br />

and environmental factors such as fog, pollution, or salt spray. Longer insulators, with longer<br />

creepage distance for leakage current, are required in these cases. Strain insulators must be<br />

strong enough mechanically to support the full weight of the span of conductor, as well as loads<br />

due to ice accumulation, and wind.<br />

Porcelain insulators may have a semi-conductive glaze finish, so that a small current (a few<br />

milliamperes) passes through the insulator.<br />

8


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

This warms the surface slightly and reduces the effect of fog and dirt accumulation. The<br />

semiconducting glaze also insures a more even <strong>distribution</strong> of voltage along the length of the<br />

chain of insulator units.<br />

Insulators for very high voltages, exceeding 200 kV, may have grading rings installed at their<br />

terminals.<br />

This improves the electric field <strong>distribution</strong> around the insulator and makes it more resistant to<br />

flash-over during voltage surges.<br />

Conductors<br />

Aluminum conductors reinforced with steel (known as ACSR) are primarily used for medium and<br />

high voltage lines and may also be used for <strong>overhead</strong> services to individual customers. Aluminum<br />

conductors are used as it has the advantage of better resistivity/weight than copper, as well as<br />

being cheaper. Some copper cable is still used, especially at lower voltages and for grounding.<br />

While larger conductors may lose less energy due to lower electrical resistance, they are more<br />

costly than smaller conductors.<br />

An optimization rule called Kelvin's Law states that the optimum size of conductor for a line is<br />

found when the cost of the energy wasted in the conductor is equal to the annual interest paid on<br />

that portion of the line construction cost due to the size of the conductors.<br />

The optimization problem is made more complex due to additional factors such as varying annual<br />

load, varying cost of installation, and by the fact that only definite discrete sizes of cable are<br />

commonly made.<br />

Since a conductor is a flexible object with uniform weight per unit length, the geometric shape of a<br />

conductor strung on towers approximates that of a catenary.<br />

The sag of the conductor (vertical distance between the highest and lowest point of the curve)<br />

varies depending on the temperature.<br />

A minimum <strong>overhead</strong> clearance must be maintained for safety.<br />

Since the temperature of the conductor increases with increasing heat produced by the current<br />

through it, it is sometimes possible to increase the power handling capacity (uprate) by changing<br />

the conductors for a type with a lower coefficient of thermal expansion or a higher allowable<br />

operating temperature.<br />

Bundled conductors are used for voltages over 200 kV to avoid corona losses and audible noise.<br />

Bundle conductors consist of several conductor cables connected by non-conducting spacers.<br />

For 220 kV lines, two-conductor bundles are usually used, for 380 kV lines usually three or even<br />

four. American Electric Power is building 765 kV lines using six conductors per phase in a bundle.<br />

Spacers must resist the forces due to wind, and magnetic forces during a short-circuit.<br />

Overhead power lines are often equipped with a ground conductor (shield wire or <strong>overhead</strong> earth<br />

wire).<br />

A ground conductor is a conductor that is usually grounded (earthed) at the top of the supporting<br />

structure to minimise the likelihood of direct lightning strikes to the phase conductors.<br />

The ground wire is also a parallel path with the earth for fault currents in earthed neutral circuits.<br />

Very high-voltage transmission lines may have two ground conductors.<br />

These are either at the outermost ends of the highest cross beam, at two V-shaped mast points,<br />

or at a separate cross arm.<br />

Older lines may use surge arrestors every few spans in place of a shield wire, this configuration is<br />

typically found in the more rural areas of the United States.<br />

By protecting the line from lightning, the design of apparatus in substations is simplified due to<br />

lower stress on insulation.<br />

Shield wires on transmission lines may include optical fibers (OPGW), used for communication<br />

and control of the power system.<br />

Medium-voltage <strong>distribution</strong> lines may have the grounded conductor strung below the phase<br />

conductors to provide some measure of protection against tall vehicles or equipment touching the<br />

energized line, as well as to provide a neutral line in Wye wired <strong>systems</strong>.<br />

9


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

While <strong>overhead</strong> lines are usually bare conductors, rarely <strong>overhead</strong> insulated cables are used,<br />

usually for short distances (less than a kilometer). Insulated cables can be directly fastened to<br />

structures without insulating supports.<br />

An <strong>overhead</strong> line with bare conductors insulated by air is typically less costly than a cable with<br />

insulated conductors.<br />

A more common approach is "covered" line wire. It is treated as bare cable, but often is safer for<br />

wildlife, as the insulation on the cables increases the likelihood of a large wing-span raptor to<br />

survive a brush with the lines, and reduces the overall danger of the lines slightly. These types of<br />

lines are often seen in the eastern United States and in heavily wooded areas, where tree-line<br />

contact is likely.<br />

The only pitfall is cost, as insulated wire is often costlier than its bare counterpart.<br />

Many utility companies implement covered line wire as jumper material where the wires are often<br />

closer to each other on the pole, such as an underground riser/Pothead, and on reclosers, cutouts<br />

and the like.<br />

Aerial bundled cable<br />

Low voltage <strong>overhead</strong> lines may use either bare conductors carried<br />

on glass or ceramic insulators or an aerial bundled cable system.<br />

The number of conductors may be anywhere between four (three<br />

phase plus a combined earth/neutral conductor - a TN-C earthing<br />

system) up to as many as six (three phase conductors,<br />

separate neutral and earth plus street lighting supplied by a<br />

common switch).<br />

Train power<br />

Overhead lines or <strong>overhead</strong> wires are used to transmit electrical energy to trams, trolleybuses or<br />

trains.<br />

Overhead line is designed on the principle of one or more <strong>overhead</strong> wires situated over rail tracks.<br />

Feeder stations at regular intervals along the <strong>overhead</strong> line supply power from the high voltage<br />

grid. For some cases low-frequency AC is used, and distributed by a special traction current<br />

network.<br />

Further applications<br />

Overhead lines are also occasionally used to supply transmitting antennas, especially for efficient<br />

transmission of long, medium and short waves.<br />

For this purpose a staggered array line is often used.<br />

Along a staggered array line the conductor cables for the supply of the earth net of the<br />

transmitting antenna are attached on the exterior of a ring, while the conductor inside the ring, is<br />

fastened to insulators leading to the high voltage standing feeder of the antenna.<br />

10


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Usage of area under <strong>overhead</strong> power lines<br />

Use of the area below an <strong>overhead</strong> line is restricted because objects must not come too close to<br />

the energized conductors. Overhead lines and structures may shed ice, creating a hazard.<br />

Radio reception can be impaired under a power line, due both to shielding of a receiver antenna<br />

by the <strong>overhead</strong> conductors, and by partial discharge at insulators and sharp points of the<br />

conductors which creates radio noise.<br />

In the area surrounding <strong>overhead</strong> lines it is dangerous to risk interference; e.g. flying kites or<br />

balloons, using ladders or operating machinery.<br />

Overhead <strong>distribution</strong> and transmission lines near airfields are often marked on maps, and the<br />

lines themselves marked with conspicuous plastic reflectors, to warn pilots of the presence of<br />

conductors.<br />

Construction of <strong>overhead</strong> power lines, especially in wilderness areas, may have significant<br />

environmental effects.<br />

Environmental studies for such projects may consider the effect of brush clearing, changed<br />

migration routes for migratory animals, possible access by predators and humans along<br />

transmission corridors, disturbances of fish habitat at stream crossings, and other effects.<br />

11


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Electricity Power Supply Systems<br />

The generation and supply of electrical energy to customers is an important part of the community<br />

in which we live to-day.<br />

Within Australia, this is generally separated into the sections of generation, transmission (with<br />

subtransmission) and <strong>distribution</strong>. Figure 1 shows a simple sketch of a system to help you<br />

visualise these various sections.<br />

In most states, the management and control of generation transmission and <strong>distribution</strong> are being<br />

separated as a matter of governmental policy, to provide competition between various generating<br />

authorities and supply authorities and to improve service.<br />

As shown in Figure 1, the extent of voltages falling within the responsibility of supply authorities is<br />

generally 132kV and below, with some 66kV in rural areas.<br />

Another aspect of the supply of electrical energy to customers is the increase in supplementary<br />

generation, sometimes by individual customers.<br />

This can be either local generation or cogeneration, both of which are operated in conjunction<br />

with the supply from the transmission system or the supply authority.<br />

The many features of cogeneration (which includes heat recovery from spent fuel) are covered in<br />

another subject.<br />

Distribution Systems and Voltage Levels<br />

Various Voltage Levels in Distribution<br />

In older <strong>systems</strong> the supply authority collects the bulk energy at 66 kV or less from the<br />

transmission substation.<br />

As indicated in Figure 1, there are specific voltage values used in the <strong>distribution</strong> of electrical<br />

power.<br />

These voltage values, which are all ‘line to line’ values are 66kV, 22kV, 11kV, 6.6kV and<br />

400/230V.<br />

Some of these values are rarely used in public <strong>distribution</strong> networks but are common in private<br />

networks in large industrial sites (eg 3.3kV, 6.6kV).<br />

Considered in its most simple form, electric power <strong>distribution</strong> consists of two main elements - (i)<br />

the retail function, or buying and selling of electrical energy and (ii) the <strong>distribution</strong> function, which<br />

is the transport and dissemination of the power.<br />

These functions have been recognised as being quite separate and financially separated from<br />

one another in the new competitive electricity market which has been set up in Australia in recent<br />

years.<br />

As electricity is not ‘stored’, many aspects of <strong>distribution</strong> are influenced by minimising the costs<br />

associated with the (instantaneous) ‘buy and sell’ operation.<br />

The choice of voltage to be used on any particular section in the <strong>distribution</strong> system will be<br />

influenced, among other factors, by:<br />

• decisions associated with voltage drops resulting from large current loads<br />

• capital cost of transformers used to change voltage levels<br />

• capital costs of construction of <strong>distribution</strong> lines and associated switchgear to operate at<br />

the chosen voltage<br />

• environmental aspects of the system installation.<br />

12


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

G Y<br />

TRANSMISSION<br />

500 or 330 kV<br />

Y Y Y Y Y<br />

Terminal<br />

station<br />

transformer<br />

with on-load<br />

tap changer<br />

SUBTRANSMISSION<br />

66 kV<br />

Zone<br />

substation<br />

transformer<br />

with on-load<br />

tap changer<br />

DISTRIBUTION<br />

22, 11 or 6.6 kV<br />

Figure 1. A simple power system<br />

13<br />

Y<br />

R<br />

Distribution transformer with<br />

off-load tap changer<br />

400 / 230 V<br />

<strong>distribution</strong><br />

Regulator<br />

to boost<br />

<strong>distribution</strong><br />

HV where<br />

required<br />

22, 11 or 6.6 kV<br />

<strong>distribution</strong>


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

For any given electrical load (in kVA), the higher the load voltage the lower will be the resultant<br />

current required.<br />

As it is the current flowing in the supply cabling which creates the voltage drop and the heating<br />

(I2R) loss, to minimise losses we try to keep the values of line current as low as possible. In this<br />

way the necessary <strong>distribution</strong> line voltage level can be determined, along with the resultant cost<br />

of constructing the line.<br />

This explains why bulk generation and transmission, where large quantities of power are<br />

produced in big ‘base-load’ generation stations and transmitted to major load centres, is done at<br />

very high voltages.<br />

This also explains why, with the exception of the low voltage <strong>distribution</strong> network, where voltages<br />

are set at 230 volts single phase/400 volts three phase, the highest voltages practical are used<br />

throughout all <strong>distribution</strong>, subtransmission and transmission <strong>systems</strong>.<br />

Because of the large cost differential between having electricity cables (conductors) <strong>overhead</strong>,<br />

suspended on insulators fixed to poles, or underground, in heavily insulated cables, many<br />

<strong>distribution</strong> <strong>systems</strong> are <strong>overhead</strong>, this being the cheaper system.<br />

However, current design tends toward placing <strong>distribution</strong> assets underground for both aesthetic<br />

and practical reasons – communities prefer a “cleaner” skyline and underground assets are less<br />

likely to be damaged (car accidents, building site cranes, etc).<br />

Types of <strong>distribution</strong> feeder <strong>systems</strong><br />

Radial<br />

Many <strong>distribution</strong> <strong>systems</strong> operate using a ‘radial feeder’ system. A typical radial feeder system is<br />

shown schematically in Figure 2.<br />

CB<br />

Zone substation 22, 11 or 6.6 kV bus<br />

CB CB CB<br />

CB<br />

22, 11 or 6.6 kV radial feeders<br />

Figure 2. Radial feeder system<br />

Radial feeders are the simplest and least expensive, both to construct and for their protection<br />

system.<br />

This advantage however is offset by the difficulty of maintaining supply in the event of a fault<br />

occurring in the feeder.<br />

A fault would result in the loss of supply to a number of customers until the fault is located and<br />

cleared.<br />

The next level of reliability is given by a ‘parallel feeder’ system.<br />

14<br />

Circuit<br />

breakers


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Parallel feeders<br />

A greater level of reliability at a higher cost is achieved with a parallel feeder. A typical parallel<br />

feeder system is shown schematically in Figure 3.<br />

In the event of a line fault only one of the feeder sets of cables will be affected, thus allowing the<br />

remaining parallel feeder to continue to supply the load.<br />

To improve the reliability factor it may be possible to have the separate sets of cables follow<br />

different routes.<br />

In this case the capital cost is double that of a radial feeder but there is a greater reliability factor<br />

for the line.<br />

This may be justified if the load is higher, more customers are being supplied, or there are loads<br />

such as hospitals which require high levels of reliability.<br />

Parallel feeders are more common in urban areas or for feeders to large single customers, where<br />

load shedding in an emergency may be possible.<br />

Typically, a<br />

large<br />

industrial<br />

customer<br />

CB Subtransmission 66 kV bus<br />

CB<br />

Y<br />

Y<br />

CB<br />

66/22, 11 or 6.6 kV transformers<br />

Zone substation 22, 11 or 6.6 kV bus<br />

CB CB CB<br />

CB<br />

22, 11 or 6.6 kV parallel feeders usually<br />

routed from substation to load centre using<br />

different routes.<br />

Figure 3. Parallel feeder system<br />

15<br />

Y<br />

Y<br />

CB<br />

Circuit<br />

breakers


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Ring main<br />

A similar level of system reliability to that of the parallel arrangement can be achieved by using<br />

‘ring main’ feeders.<br />

This usually results from the growth of load supplied by a parallel feeder where the cabling has<br />

been installed along different routes.<br />

These are most common in urban and industrial environments.<br />

Whilst the start and finish ends of the ring are at the same location, power is delivered by both<br />

pathways of the ring into substations located around the ring.<br />

Should a fault occur on a feeder cable at any point around the ring the faulty section may be<br />

isolated by the operation of the protecting circuit breakers, at the same time maintaining supply to<br />

all substations on the ring.<br />

In typical urban/suburban ring-main arrangements, the open ring is operated manually and loss of<br />

supply restored by manual switching.<br />

Current practice is to use ‘<strong>distribution</strong> automation’, where operation and supply restoration in the<br />

feeder rings is done automatically by centrally-controlled supervisory <strong>systems</strong>.<br />

This gives the advantages of ring main <strong>systems</strong> as line voltage drops are reduced at the various<br />

load Substations there is a ‘firm’ supply (ie an alternative path is available if the primary one fails)<br />

to each load substation.<br />

Zone<br />

Substations<br />

CB CB<br />

CB CB CB CB CB CB CB CB<br />

CB CB CB CB<br />

CB CB CB CB<br />

Figure 4. A ring main feeder system<br />

Meshed <strong>systems</strong><br />

In transmission and sub-transmission <strong>systems</strong>, usually parallel, ring or interconnected (‘mesh’)<br />

<strong>systems</strong> are used.<br />

This ensures that alternative supply can be made to customers in the event of failure of a<br />

transmission line or element.<br />

The extra expense can be justified because of the much greater load and number of customers<br />

that are affected by failure of lines at transmission or sub-transmission levels. The general rule is<br />

that where large loads or numbers of customers are involved, then some form of standby, in the<br />

form of deliberate redundancy, is built into the network design, through the use of parallel,<br />

meshed or ring type feeders.<br />

Only in outer rural areas would one consider using only radial supply at a sub-transmission level.<br />

On the other hand, simple radial supply is almost universally used for low voltage (400V) feeders,<br />

even in urban areas, because they supply relatively few customers.<br />

16<br />

Terminal Station


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Revision exercise 1<br />

1. List the voltage levels used in the various stages of transmission and <strong>distribution</strong> in<br />

electric power <strong>systems</strong>.<br />

2. List the main sections of a power system, starting with the generators and ending with<br />

the customer’s load?<br />

3. State where one would use each of the following types of feeders. Give reasons in<br />

each case.<br />

a. Radial feeders<br />

b. Parallel feeders<br />

c. Ring feeders<br />

d. Meshed feeders<br />

4. How can the cost of the higher-level feeder <strong>systems</strong> be justified?<br />

17


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Overhead and Underground Power Systems<br />

As stated previously, initial <strong>overhead</strong> line construction is less expensive than underground cabling<br />

for the same kVA load. In rural or semi-rural areas, the sheer cost of underground cabling would<br />

make it impossible for customers to be able to afford the cost of supply.<br />

The down side is that <strong>overhead</strong> lines operate under continual mechanical stress with exposure to<br />

varying climatic conditions.<br />

This results in progressive deterioration in time as a result of corrosion, mechanical wear and<br />

fatigue, timber rot, etc.<br />

All components must be periodically inspected and replaced as required. They are exposed to<br />

environmental impacts such as storms, lightning, wind-blown debris and traffic impact (of poles)<br />

which means <strong>overhead</strong> <strong>systems</strong> are rarely as reliable as underground ones.<br />

The greater spacing of <strong>overhead</strong> line conductors generally results in higher system inductance<br />

than for a cable system.<br />

This means an <strong>overhead</strong> line has a greater voltage drop than an underground cable of equal<br />

current-carrying capacity and hence cannot supply power over as long a distance as the<br />

underground equivalent, particularly for lower voltage <strong>distribution</strong> <strong>systems</strong>.<br />

Even though poles are considered unsightly in urban locations, the capacity of an <strong>overhead</strong><br />

feeder can be readily increased by replacing it with larger conductors and/or increasing the<br />

voltage insulation/operating level.<br />

This flexibility is one big advantage of <strong>overhead</strong> <strong>systems</strong>.<br />

The reliability of underground <strong>distribution</strong> is greater than for <strong>overhead</strong> <strong>systems</strong> because of the<br />

lower number of fault interruptions, as discussed above.<br />

However, when interruptions do occur they are generally of much longer duration than those<br />

associated with <strong>overhead</strong> lines.<br />

Underground cables have comparatively higher capacitance, and under light load conditions can<br />

affect system power factor.<br />

In some cases, high charging currents and high transient voltages may accompany switching of<br />

cable <strong>systems</strong> that are open-circuited (especially at the higher <strong>distribution</strong> voltages, eg 22kV).<br />

This light-load performance can limit total underground feeder length.<br />

On the other hand, this does mean they can supply heavy load, especially when it is inductive in<br />

nature, over longer distances than <strong>overhead</strong> lines.<br />

The cost of underground cabling includes:<br />

• the cost of trenching (and sometimes compensation for private amenity) coping with<br />

obstructions from other utilities such as gas, water, sewerage / drainage, telephone, etc<br />

• the reinstatement of footpaths and road surfaces.<br />

• The subsequent installation of another underground cable along the same path for system<br />

reinforcement by a parallel or ring feeder, generally only exacerbates these difficulties.<br />

18


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Overhead Insulated Conductors<br />

A more recent development has been the use of <strong>overhead</strong> conductors which are insulated.<br />

These conductors are more expensive than bare <strong>overhead</strong> but cheaper than full underground, as<br />

full cable outer mechanical protection is not needed, nor is expensive trenching and restoration.<br />

Being insulated provides some protection against wind-blown debris short-circuiting conductors<br />

together or conductor clashing.<br />

There are two basic types:<br />

1. Aerial bundled cable, or ABC for short, consisting of fully insulated (ie safe to touch)<br />

conductors tightly wrapped around a mechanical bearer wire (usually steel).<br />

2. Covered conductors, consisting of ‘partly insulated’ conductors mounted on insulators<br />

similar to bare <strong>overhead</strong> lines. These are cheaper than ABC and offer most of the<br />

protection features against wind-blown debris as does ABC but are not touch safe.<br />

ABC in particular is heavy and unsightly requiring more poles than bare-wire <strong>overhead</strong>, but trees<br />

can grow around it and hide it almost completely from view in due course. Covered conductor can<br />

also tolerate trees near it, but not to the same extent as ABC. It is less heavy and less unsightly<br />

when not shielded by trees.<br />

Revision exercise 2<br />

1. What are the three main types of conductor/cable <strong>systems</strong> used in <strong>distribution</strong>?<br />

2. What are the advantages and disadvantages of underground <strong>distribution</strong> cable<br />

networks?<br />

3. Where would one use aerial insulated conductor <strong>systems</strong> instead of either bare wire<br />

<strong>overhead</strong> or underground <strong>systems</strong>?<br />

19


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Three Phase, Single Phase and Single Wire Earth Return Systems<br />

By far the majority of customers have electricity supplied to their homes, offices, factories, etc. as<br />

a three phase and/or single phase supply at voltages of 400 volts and/or 230 volts.<br />

Most houses are supplied at 230 volt single phase, as this is cheapest for light loads, involving<br />

only two wires.<br />

Medium sized ‘business’ customers (ie, factories, shops) will normally be supplied at 400 volt<br />

three-phase.<br />

This involves running four wires into the customer and is still cost effective in urban areas<br />

because the street supply is always three phase.<br />

The low voltage consists of three 230 Volt active phases and one ‘neutral’.<br />

The neutrals are then connected to the customers load using the MEN system of earthing.<br />

This provides a low resistance connection to earth providing protection to both the customers and<br />

the supply system in the event of faults.<br />

Large customers cannot be supplied economically at 400/230 volts because of the high cost of<br />

providing all the cabling that would be required.<br />

nstead, such customers (eg mines, large industrial sites, large commercial centres) are usually<br />

supplied at a high voltage instead of the conventional 400/230 Volts.<br />

In this case the customer would usually own (or lease) the power transformer or transformers<br />

needed to reduce the high voltage supply, and in return the customer would have a lower tariff for<br />

energy consumed.<br />

High voltage single phase <strong>systems</strong> are commonplace in rural areas, where the cost of supplying<br />

customers with relatively small loads at remote locations is a major problem. In such areas, the<br />

high voltage (usually 22kV or 11kV) feeder has only two wires and substations only supply one<br />

customer or a small group of customers close together, eg a farm and its associated outbuildings).<br />

There is no real low voltage network, other than single phase supply direct to the farm buildings.<br />

In such situations, the method used is to arrange the 22/11 kV <strong>overhead</strong> line to pass as close as<br />

practical to most of the customers.<br />

At the nearest pole to a customer a double wound single phase pole mounted transformer is<br />

connected with the primary across the two high voltage wires and the secondary providing<br />

nominally 230 volts, as a single phase to neutral supply.<br />

Single wire earth return (SWER) or single wire ground return is a single-wire transmission line for<br />

supplying single-phase electrical power from an electrical grid to remote areas at low cost.<br />

It is principally used for rural electrification, but also finds use for larger isolated loads such as<br />

water pumps, and light rail.<br />

Single wire earth return is also used for HVDC over submarine power cables.<br />

20


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Description<br />

SWER is a choice for a <strong>distribution</strong> system when conventional return current wiring would cost<br />

more than SWER’s isolation transformers and small power losses.<br />

Power engineers experienced with both SWER and conventional power lines rate SWER as<br />

equally safe, more reliable, less costly, but with slightly lower efficiency than conventional lines.<br />

Some single wire transmission proposals have used radio-frequency AC.<br />

SWER uses conventional 50Hz or 60Hz AC power, and is therefore much less expensive.<br />

Conventional low frequency 50Hz or 60Hz power is supplied to the SWER line by an isolating<br />

transformer of up to 300 kVA.<br />

This transformer isolates the grid from ground or earth, and changes the grid voltage (typically 22<br />

kilovolts line to line) to the SWER voltage (typically 12.7 or 19.1 kilovolts line to earth).<br />

SWER line<br />

21


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

The SWER line is a single conductor that may stretch for tens or even hundreds of kilometres,<br />

visiting a number of termination points.<br />

At each termination point, such as a customer's premises, current flows from the line, through the<br />

primary coil of a step-down transformer, to earth through an earth stake.<br />

From the earth stake, the current eventually finds its way back to the main step-down transformer<br />

at the head of the line, completing the circuit.<br />

SWER is therefore a practical example of a phantom loop.<br />

SWER burns up grounding poles or may fail to reset breakers in areas with high resistance soil.<br />

In Australia, locations with very dry soils need the grounding poles to be extra deep.<br />

Experience in Alaska shows that SWER needs to be grounded below permafrost, which is highresistance.<br />

The secondary winding of the local transformer will supply the customer with either single ended<br />

single phase (N-0) or split phase (N-0-N) power in the region’s standard appliance voltages, with<br />

the 0 volt line connected to a safety earth that does not normally carry an operating current.<br />

A large SWER line may feed as many as 80 <strong>distribution</strong> transformers.<br />

The transformers are usually rated at 5 kVA, 10 kVA and 25 kVA. The load densities are usually<br />

below 0.5 kVA per kilometer (0.8 kVA per mile) of line.<br />

Any single customer’s maximum demand will typically be less than 3.5 kVA, but larger loads up to<br />

the capacity of the <strong>distribution</strong> transformer can also be supplied.<br />

Some SWER <strong>systems</strong> in the USA are conventional <strong>distribution</strong> feeders that were built without a<br />

continuous neutral (some of which were obsoleted transmission lines that were refitted for rural<br />

<strong>distribution</strong> service).<br />

The substation feeding such lines has a grounding rod on each pole within the substation; then on<br />

each branch from the line, the span between the pole next to and the pole carrying the<br />

transformer would have a grounded conductor (giving each transformer two grounding points for<br />

safety reasons).<br />

22


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

History<br />

At the end of the 19th century, Nikola Tesla demonstrated that only a single wire was necessary<br />

for power <strong>systems</strong>, with no need for a wired return conductor (using the Earth instead).<br />

Lloyd Mandeno fully developed SWER in New Zealand around 1925 for rural electrification.<br />

Although he termed it “Earth Working Single Wire Line” it was often called “Mandeno’s<br />

Clothesline”. More than 200,000 kilometres have now been installed in Australia and New<br />

Zealand.<br />

It is considered safe, reliable and low cost, provided that safety features and earthing are correctly<br />

installed.<br />

The Australian standards are widely used and cited. It has been applied in Saskatchewan of<br />

Canada, Brazil, Africa, portions of the United States' Upper Midwest, and SWER interties have<br />

been proposed for Alaska and prototyped.<br />

Characteristics<br />

Safety<br />

SWER violates common wisdom about electrical safety, because it lacks a traditional metallic<br />

return to a neutral shared by the generator.<br />

SWER’s safety is instead assured because transformers isolate the ground from both the<br />

generator and user.<br />

However, certain groups claim that stray voltages from SWER can injure livestock.<br />

Grounding is critical because of the significant currents on the order of 8 amperes that flow<br />

through the ground near the earth points, so a good-quality earth connection is needed to prevent<br />

risk of electric shock due to earth potential rise near this point.<br />

Separate grounds for power and safety are also used.<br />

Duplication of the ground points assures that the system is still safe if either of the grounds is<br />

damaged.<br />

A good earth connection is normally a 6 m stake of copper-clad steel driven vertically into the<br />

ground, and bonded to the transformer earth and tank.<br />

A good ground resistance is 5–10 ohms.<br />

SWER <strong>systems</strong> are designed to limit the voltage in the earth to 20 volts per meter to avoid<br />

shocking people and animals that might be in the area.<br />

Other standard features include automatic reclosing circuit breakers (reclosers).<br />

Most faults (over-current) are transient.<br />

Since the network is rural, most of these faults will be cleared by the recloser.<br />

Each service site needs a rewirable drop out fuse for protection and switching of the transformer.<br />

The transformer secondary should also be protected by a standard high-rupture capacity (HRC)<br />

fuse or low voltage circuit breaker.<br />

A surge arrestor (spark gap) on the high voltage side is common, especially in lightning-prone<br />

areas.<br />

Bare-wire or ground-return telecommunications can be compromised by the ground-return current<br />

if the grounding area is closer than 100 m or sinks more than 10 A of current.<br />

Modern radio, optic fibre channels and cell phone <strong>systems</strong> are unaffected.<br />

23


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Cost advantage<br />

SWER’s main advantage is its low cost.<br />

It is often used in sparsely populated areas where the cost of building an isolated <strong>distribution</strong> line<br />

cannot be justified.<br />

Capital costs are roughly 50% of an equivalent two-wire single-phase line.<br />

They can be 70% less than 3-wire three-phase <strong>systems</strong>.<br />

Maintenance costs are roughly 50% of an equivalent line.<br />

SWER also reduces the largest cost of a <strong>distribution</strong> network, the number of poles.<br />

Conventional 2-wire or 3-wire <strong>distribution</strong> lines have a higher power transfer capacity, but can<br />

require seven poles per kilometre, with spans of 100 m to 150 m. SWER’s high line voltage and<br />

low current permits the use of low-cost galvanized steel wire.<br />

Steel’s greater strength permits spans of 400 m or more, reducing the number of poles to 2.5 per<br />

kilometre.<br />

Reinforced concrete poles have been traditionally used in SWER lines because of their low cost,<br />

low maintenance, and resistance to water damage, termites and fungus.<br />

Local labor can produce them in most areas, further lowering costs.<br />

If the cable contains optic fibre, or carries telephone service, this can further amortize the capital<br />

costs.<br />

Reliability strengths<br />

SWER can be used in a grid or loop, but is usually arranged in a linear or radial layout to save<br />

costs. In the customary linear form, a single-point failure in a SWER line causes all customers<br />

further down the line to lose power.<br />

However, since it has fewer components in the field, SWER has less to fail. For example, since<br />

there is only one line, winds can’t cause lines to clash, removing a source of damage, as well as a<br />

source of rural brush fires.<br />

Since the line can't clash in the wind, and the bulk of the transmission line has low resistance<br />

attachments to earth, excessive ground currents from shorts and geomagnetic storms are far<br />

more rare than in conventional metallic-return <strong>systems</strong>.<br />

So, SWER has fewer ground-fault circuit-breaker openings to interrupt service.<br />

Power quality weakness<br />

SWER lines tend to be long, with high impedance, so the voltage drop along the line is often a<br />

problem, causing poor regulation.<br />

Variations in demand cause variation in the delivered voltage.<br />

To combat this, some installations have automatic variable transformers at the customer site to<br />

keep the received voltage within legal specifications.<br />

When used with distributed generation, SWER is substantially more efficient than when it is<br />

operated as a single-ended system.<br />

For example, some rural installations can offset line losses and charging currents with local solar<br />

power, wind power, small hydro or other local generation.<br />

This can be an excellent value for the electrical distributor, because it reduces the need for more<br />

lines.[<br />

After some years of experience, the inventor advocated a capacitor in series with the ground of<br />

the main isolation transformer to counteract the inductive reactance of the transformers, wire and<br />

earth return path.<br />

The plan was to improve the power factor, reduce losses and improve voltage performance due to<br />

reactive power flow.<br />

Though theoretically sound, this is not standard practice.<br />

24


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Networks and circuits<br />

As demand grows, a well-designed SWER line can be substantially upgraded without new poles.<br />

The first step may be to replace the steel wire with more expensive copper-clad or aluminium-clad<br />

steel wire.<br />

It may be possible to increase the voltage.<br />

Some distant SWER lines now operate at voltages as high as 35 kV.<br />

Normally this requires changing the insulators and transformers, but no new poles are needed.<br />

If more capacity is needed, a second SWER line can be run on the same poles to provide two<br />

SWER lines 180 degrees out of phase.<br />

This requires more insulators and wire, but doubles the power without doubling the poles.<br />

Many standard SWER poles have several bolt holes to support this upgrade.<br />

This configuration causes most ground currents to cancel, reducing shock hazards and<br />

interference with communication wirelines.<br />

Two phase service is also possible with a two-wire upgrade:<br />

Though less reliable, it is more efficient.<br />

As more power is needed the lines can be upgraded to match the load, from single wire SWER to<br />

two wire, single phase and finally to three wire, three phase.<br />

This ensures a more efficient use of capital and makes the initial installation more affordable.<br />

Customer equipment installed before these upgrades will all be single phase, and can be reused<br />

after the upgrade.<br />

If moderate amounts of three-phase are needed, it can be economically synthesized from twophase<br />

with on-site equipment.<br />

Regulatory issues<br />

Many national electrical regulations (notably the U.S.) require a metallic return line from the load<br />

to the generator.<br />

In these jurisdictions, each SWER line must be approved by exception.<br />

Use in interties<br />

In 1981 a high-power 8.5 mile prototype SWER intertie was successfully installed from a coal<br />

plant in Bethel to Napakiak in Alaska, United States.<br />

It operates at 80 kV, and has special lightweight fiberglass poles forming an A-frame.<br />

The poles can be carried on lightweight snow machines, and most poles can be installed with<br />

hand tools on permafrost without extensive digging.<br />

Erection of “anchoring” poles still required heavy machinery, but the cost savings were dramatic.<br />

The phase conductor also carries a bundle of optical fibres within the steel armour wire, so the<br />

system supplies telecommunications as well as power.<br />

Researchers at the University of Alaska Fairbanks, United States estimate that a network of such<br />

interties, combined with coastal wind turbines, could substantially reduce Alaska’s dependence on<br />

increasingly expensive diesel fuel for power generation.<br />

Alaska’s state economic energy screening survey advocated further study of this option to use<br />

more of the state’s underutilized power sources.<br />

Use by developing nations<br />

At present, certain developing nations have adopted SWER-<strong>systems</strong> as their mains electricity<br />

<strong>systems</strong>. Notably Laos and South Africa.<br />

25


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Use for HVDC <strong>systems</strong><br />

Many HVDC <strong>systems</strong> using submarine power cables are (or were until their expansion to bipolar<br />

schemes) single wire earth return <strong>systems</strong>.<br />

To avoid electrochemical corrosion, the ground electrodes of such <strong>systems</strong> are situated apart<br />

from the converter stations and not near the transmission cable.<br />

The electrodes can be situated in the sea or on land.<br />

Bare copper wires can be used for cathodes, and graphite rods buried in the ground, or titanium<br />

grids in the sea are used for anodes.<br />

To avoid electrochemical corrosion (and passivation of titanium surfaces) the current density at<br />

the surface of the electrodes may be only small and therefore large electrodes are required.<br />

The advantage of such schemes is eliminating the cost of a second conductor, since saltwater is<br />

an excellent conductor.<br />

Some ecologists claim bad influences of electrochemical reactions, but they do not occur on very<br />

large underwater electrodes.<br />

Revision Exercise 3<br />

1. Where would you expect three phase and single phase <strong>systems</strong> to be used? Why?<br />

2. How is supply provided to very large customers?<br />

26


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Supply Quality<br />

It is the aim of a well-designed electricity system to provide voltage to customers that is stable,<br />

stays within limits and is free from random momentary variations and other disturbing waveforms.<br />

The term ‘supply quality’ or ‘quality of supply’ has come to be a collective term which includes<br />

electrical power parameters such as:<br />

• voltage variation outside of standards<br />

• voltage sags and swells<br />

• repeated fluctuations<br />

• impulses (spikes)<br />

• momentary interruptions (sudden dips)<br />

• frequency variations and waveform distortion (harmonics).<br />

As well as the problems caused by such variations with computing equipment, variable speed<br />

drive controllers and other sensitive electronic controls, there can also be interruptions to<br />

customers resulting in loss of production or amenity.<br />

There is also a need to ensure the robustness of a supply, which includes its ability to continue to<br />

meet power demands under excessive loads, operation of system protection equipment, etc. The<br />

result is that greater care has to be given to what, in the past, may have been considered ‘risk<br />

factors’ that the customer was once expected to simply put up with as a part of his electricity<br />

supply.<br />

Some of the more established factors considered in supply quality are now listed and discussed.<br />

Voltage and frequency Stability<br />

Standards and legislation in the various countries set out the values and acceptable tolerances on<br />

voltage and frequency values allowable from a distributor.<br />

If frequency varies even by small amounts from the nominal 50 hertz (cycles per second) this will<br />

cause problems for generation equipment and to customers.<br />

Once system frequency falls as low as only 49.5 Hz the system usually is on the verge of<br />

collapse.<br />

From a customer’s perspective, voltages which are too high will severely reduce the life of<br />

incandescent lamps and possibly damage sensitive equipment, whilst voltage values which are<br />

too low will significantly increase the current drawn (relative to the rated current and voltage) for<br />

any motor driven loads, resulting in possible thermal damage to motors and reduce the<br />

starting/pull-out torques of motors.<br />

For these reasons considerable care needs to be taken to ensure that voltage values are held<br />

stable during the daily cycle of load changes.<br />

The maximum variation in voltage (ie difference between highest and lowest voltage) is referred<br />

to as ‘voltage spread’, ‘variation’ or ‘bandwidth’.<br />

This is usually expressed as a percentage of the nominal voltage.<br />

In Australia, standards set the maximum voltage regulation for 230 volt <strong>systems</strong> to be 230 volts<br />

plus 10% or minus 14%, ie a maximum of 253 volts and a minimum of 198 volts for all except<br />

emergency conditions.<br />

Voltage Fluctuations<br />

Rapidly varying loads, ie those where the current drawn from the power system goes up and<br />

down in magnitude frequently, cause voltage drops in the system which is also rapidly varying<br />

and consequently other customers are subjected to them.<br />

This is an additional problem on top of the slow variations in voltage throughout the day discussed<br />

above.<br />

Loads of this nature include electric motors which start up, run and shut down (or go from light to<br />

full load and back again) frequently, eg rolling mills, metal shredders, as well as arc welders and<br />

the like.<br />

The voltage drop can be seen by customers as a dip in the output of lights; if it occurs frequently it<br />

causes a flickering of the lights which can be extremely annoying.<br />

27


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

The more rapid the flicker, the worse the visual distress that is caused.<br />

There are standards which limit the amount and frequency of such voltage fluctuations on the<br />

system.<br />

Momentary Interruptions<br />

Another problem somewhat akin to voltage fluctuations is momentary interruptions to supply.<br />

These can occur for a number of reasons, usually when transient faults on the system may cause<br />

a large but very brief voltage dip on the system, or when the primary supply may fail and the<br />

system will switch across to a standby supply, eg on a ‘ring’ system.<br />

The effect is sometimes low or no supply from less than a second to maybe several seconds.<br />

Normally this will be of minor inconvenience, often hardly noticed by most customers.<br />

It does cause problems for voltage sensitive equipment such as computers, digital clocks which<br />

often have to be reset and to ‘undervoltage’ relays on large electric motors, which often will trip<br />

the motor out (on the mistaken assumption that the voltage will stay low and the motor overheat).<br />

In the past momentary interruptions rarely caused problems but with increasing numbers of<br />

voltage sensitive devices, especially electronic and digital ones, it is becoming a major issue for<br />

electricity distributors.<br />

Revision Exercise 4<br />

1. What are the main areas of concern under the broad definition of ‘supply quality’?<br />

2. What problems can be caused by the following power supply variations?<br />

a) Excessive voltage<br />

b) Too low a voltage<br />

28


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

3. Why are momentary dips on the system more of a problem now than they used to be?<br />

Power Factor Considerations<br />

As most electrical loads are inductive, and <strong>distribution</strong> lines, when loaded, are also inductive, a<br />

heavily loaded <strong>distribution</strong> system usually appears to be an inductive impedance and operates at<br />

a ‘lagging’ power factor.<br />

This means that the current sine wave lags somewhat behind the voltage sine wave.<br />

Depending on the line construction and its length, a lightly-loaded or open circuit <strong>overhead</strong> line<br />

may appear to be a capacitive load.<br />

This means the current now leads the voltage and reduces voltage drop, but causes other<br />

complications including sometimes voltages which are too high at the receiving end.<br />

The component (ie proportion) of the current in phase with the voltage sine wave represents the<br />

actual energy supplied by the system.<br />

The rest of the current doesn’t supply useful energy to the customer and causes unwanted<br />

voltage drops and losses in the <strong>distribution</strong> system.<br />

As the customers typically pay for energy in kilowatt-hours, to make best use of the current<br />

carrying capacity of a line we endeavour to minimise the reactive current component carried in the<br />

system. (This is determined by the amount of inductance and capacitance in the system.)<br />

This can be achieved in a number of ways, the most popular of which is capacitor power factor<br />

correction at substations throughout the system.<br />

This consists of adding shunt (ie from each phase to ground) capacitors, which increases the<br />

capacitance at selected points to directly counteract the inductance in the system, or the<br />

customers’ loads.<br />

Waveform Distortion and Harmonics<br />

Ideally, a power system should have voltages and currents which are pure sine-waves.<br />

The ever increasing use of fluorescent lighting and electronic light dimmers, industrial rectifiers,<br />

variable speed motor drive equipment and computers (with switched mode power supplies)<br />

results in severe distortion of the sinusoidal waveform of the voltage in the <strong>distribution</strong> system.<br />

As this electronic equipment is usually connected by the customer the distributor has little control<br />

over the extent of the equipment connected but must, on the other hand, ensure the supply<br />

complies with the relevant requirements.<br />

The analysis of the effect of waveform distortion is usually done by considering the magnitude of<br />

the various harmonic components of the voltage which are present to create this distort it in<br />

Instruments are available to measure the relative magnitudes of the harmonics present.<br />

Harmonics are classified as ‘odd’ or ‘even’, depending on the numeric factor by which their<br />

frequency varies from the fundamental frequency (of 50 hertz).<br />

29


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Harmonics are also classified into groups designated as ‘positive’, ‘negative’ and ‘zero’ sequence<br />

values or components.<br />

Frequency Harmonic<br />

(Hertz) Identification Odd / Even Sequence<br />

50 Fundamental Positive<br />

100 2 ND Even Negative<br />

150 3 RD Odd Zero<br />

200 4 TH Even Positive<br />

250 5 TH Odd Negative<br />

300 6 TH Even Zero<br />

350 7 TH Odd Positive<br />

400 8 TH Even Negative<br />

450 9 TH Odd Zero<br />

500 etc Even<br />

Note: The fundamental can be thought of as an odd harmonic. A DC component,<br />

if present, is essentially a “zero” harmonic (at 0 hz) and is zero sequence,<br />

flowing down all phases to ground. This would fit into the overall pattern.<br />

Table 1. Sequencing and Frequencies of Fundamental and harmonic Currents<br />

(based on 50 Hz system)<br />

Whenever a neutral/earth connection is made, any ‘zero’ sequence components of current<br />

(resulting from corresponding voltages in the system) will flow to the ‘ground’.<br />

If these values of current are significant (i.e. greater than 15% of the values of line currents) there<br />

can be a measurable voltage drop created in the neutral/earth connection.<br />

The effect of this voltage drop is to ‘move’ the neutral (star point) voltage, and this can result in<br />

excessively high or low voltage values being applied to any connected equipment.<br />

Other problems which result from harmonic distortion are manifest at or near the ‘earth stake’<br />

location, where it is possible for dangerously high voltage values to result on the surface of the<br />

soil, or heating of the soil can occur, due to high earth current density.<br />

Harmonics, especially the ‘negative sequence’ ones, cause overheating problems in electric<br />

motors and harmonics of all types interfere with electronic and computer-based equipment.<br />

30


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Revision exercise 5<br />

1. Describe what power factor means and how it can be controlled.<br />

2. List the main problems caused by harmonics in a power system.<br />

31


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Voltage Regulation<br />

Voltage variation is the variation in the magnitude of the voltage value between its highest and<br />

lowest levels that occurs as the connected load changes between maximum and minimum.<br />

Voltage regulation, in an item of plant such as a transformer, or down a feeder, is the drop in<br />

voltage which occurs from the supply end to the connected load.<br />

Both are usually expressed as a ratio or percentage of the load voltage. For an <strong>overhead</strong> line it<br />

can be defined mathematically as<br />

Voltage Regulation<br />

ES − E<br />

=<br />

E<br />

where: ES is the voltage at the supply end, and<br />

ER is the voltage at the load.<br />

R<br />

R<br />

The variation of voltage at a consumer’s supply point should be kept to a minimum for the<br />

following reasons:<br />

1. When incandescent lamps are connected their performance is very sensitive to variations<br />

in the supply voltage. A five per cent reduction below rated voltage results in a decrease<br />

between fifteen and twenty per cent of the light output; a five percent increase above rated<br />

voltage shortens the ‘life’ of the lamp by up to 40%.<br />

2. Variations from rated voltage reduce the effectiveness of induction motors and<br />

transformers. When operating above rated voltage, the iron in the magnetic circuit of the<br />

motor/transformer will be closer to saturation or over saturated resulting in a larger<br />

magnetising current and greater heating of the motor/transformer. If the voltage is below<br />

the rated value, the starting torque and pull-out torque are considerably reduced and<br />

heavier currents have to be drawn which can overheat motors.<br />

3. Depending on the internal circuitry, electronic control equipment, computers and television<br />

equipment may not function adequately with wide variations in supply voltage.<br />

There is also an effect on the <strong>distribution</strong> system as operating above rated voltage causes<br />

excessive heating in <strong>distribution</strong> transformers and results in waveform distortion due to saturation<br />

of the iron, causing the introduction of third harmonic values of voltage.<br />

These also can cause heating of earth stakes and local earth potential rise problems, if they are<br />

very high.<br />

This variation in the voltage at the connected load between its highest to its lowest value is often<br />

referred to as ‘bandwidth’.<br />

Limits and standards<br />

There are accepted standards which dictate maximum voltage variations in a public electricity<br />

supply system. The international standard recently adopted in Australia is based on 230 volts<br />

rather than 240 volts, to enable standardisation of appliances, motors and the like. It specifies 230<br />

volts plus 10% minus 14% as the maximum permissible regulation.<br />

The voltages will however apply to ‘utilisation voltages’ rather than the voltage at ‘customer’s<br />

terminals’ as does the existing standard.<br />

Its important at this stage to fully understand the terminology used and these are explained in the<br />

following section.<br />

32


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Terminology<br />

Distribution system<br />

This essentially, is the feeders and substations and their ancillary equipment - poles, switches,<br />

circuit breakers, fuses plus the support equipment such as supervisory control and protection<br />

<strong>systems</strong> which makes up the public supply network.<br />

The ‘public’ network is one which is ‘shared’, ie supplies at least two or more customers over the<br />

one set of assets.<br />

A ‘private’ system is one which feeds just the one customer, even when the customer is very large<br />

and may have a private network which contains many local substations and feeders.<br />

The <strong>distribution</strong> system also means that part of the public network which operates at voltages<br />

below that defined as ‘transmission’ and typically takes voltages at medium to high levels and<br />

reduces these down for use by customers.<br />

The role and design of other ancillary equipment is covered in other courses and will not be<br />

discussed further in this module; however it is equally important to the function of the <strong>distribution</strong><br />

system as are the feeders discussed here.<br />

Customer’s terminals<br />

This is the connection point between the public <strong>distribution</strong> system and the take-off to supply<br />

individual customers.<br />

Typically for residential customers, it is the ‘barge board’ on the front of the house. For a farm it is<br />

typically the first low voltage pole just inside the property of the customer, where that take-off<br />

supplies just the one customer only.<br />

Customer voltage<br />

This is the voltage at the ‘customer’s terminals’, as defined above.<br />

As discussed previously, the current Australian standards for maximum variation in voltage refer<br />

to the voltage at the customers’ terminals.<br />

Base voltage<br />

This is the nominal voltage of the <strong>distribution</strong> system.<br />

For low voltage <strong>systems</strong> in Australia, this is almost universally 240 volts single phase/415 volts<br />

three phase.<br />

There is a separate base voltage for each voltage layer in the <strong>distribution</strong> system, eg 11 kV, 66<br />

kV, 132 kV etc.<br />

Utilisation voltage<br />

This is the voltage at the ‘point of utilisation’ i.e. the power point inside the customer’s premises. It<br />

is a more realistic representation of voltage conditions that appliances will be subject to in their<br />

typical use than is ‘customer voltage’.<br />

Under heavy loading conditions, it will be lower than the voltage at the customer’s terminals, due<br />

to the voltage drop in the customer’s wiring which runs between the customer terminals and the<br />

actual power point.<br />

The proposed 230 volts standard will recognise this by using utilisation voltage in its definition of<br />

limits rather than customer voltage.<br />

33


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Revision exercise 6<br />

1. What is the definition of:<br />

Customers’ terminals<br />

Base voltage<br />

Customer voltage<br />

Utilisation voltage<br />

2. With regard to voltage variation, what is the current 400/230 volt supply standard in<br />

Australia?<br />

3. With regard to voltage variation, what is the current low voltage supply standard in<br />

China?<br />

34


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Causes of voltage variation<br />

Voltage variations on the <strong>distribution</strong> system may result from one or more of the following causes:<br />

1. The voltage at the source (from the transmission system or generator) may not be<br />

controlled, or is controlled only within certain limits.<br />

2. The voltage at the secondary of a transformer varies as the load changes. With a large<br />

load current the voltage drop due to the transformer windings needs to be subtracted<br />

from the (open circuit) voltage of the secondary terminals (This is the voltage<br />

regulation of the transformer). As the load current decreases the terminal voltage<br />

increases, being at its greatest when there is no load current from the transformer.<br />

3. The voltage drop in the <strong>distribution</strong> lines when delivering current, due to the inherent<br />

resistance and reactance of the <strong>overhead</strong> lines.<br />

Variation of resistance of conductors<br />

The value of resistance for conductors is usually stated for an ambient temperature of 20°C,<br />

however it is not unusual for an <strong>overhead</strong> line to have conductors at temperatures up to 65°C or<br />

more in summer time with large current loads. Due to this rise in conductor temperature it is<br />

possible to have the resistance of the conductor increase by up to 20% or more. The method of<br />

calculating this increase is as follows:<br />

Starting from a value of (d.c.) resistance at 20°C, the (d.c.) resistance of the conductor at any<br />

other temperature 8°C can be calculated from:<br />

Rθ = R20[1 + α2O(θ – 20)]<br />

where: Rθ = d.c. resistance at 8°C<br />

R20 = d.c. resistance at 20°C<br />

α20 = temperature coefficient of resistance at 20°C.<br />

For copper, α20 = 0.00393 per deg C<br />

For aluminium, α20 = 0.00403 per deg C.<br />

This value then needs to be corrected to allow for the effect of a.c. voltages being applied to the<br />

conductors and the resultant slight variations in current density in the conductor, the effect of steel<br />

cores (if present) and any insulation (as in Aerial Bundled Cable or ABC). The ‘correcting value’<br />

(R’) is found by measurement (empirically) and added to the previously calculated value of Rθ, so<br />

that the effective a.c. resistance Rθ2 is given by:<br />

Rθ2 = Rθ + R’<br />

Typically this adds about 10 to 15% to the DC resistance.<br />

35


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Inductance of <strong>overhead</strong> conductors<br />

Inductance of feeders is caused by the magnetic fields around the currents (‘magnetic flux’)<br />

interacting with the conductors and inducing a reverse voltage or ‘back emf’ which opposes the<br />

current flow. This is manifest as a voltage drop in the conductors. The inductance of a nonmagnetic<br />

conductor at 50 hertz, relative to another similar conductor can be calculated from the<br />

equation:<br />

XL = 0.0156 + 0.1447 log10<br />

d<br />

milli-Henries per km<br />

r<br />

where: d = distance between conductors in metres<br />

r = radius of the conductor in metres<br />

In practice it is easier and more convenient to use pre-calculated tables for determining line<br />

reactance in ohms rather than individual calculations, or use computers and software packages<br />

such as spreadsheets.<br />

Because conductor spacings for <strong>overhead</strong> lines are necessarily large, there is not a great deal of<br />

variation in <strong>overhead</strong> line reactance values for various conductors.<br />

Schedules showing some selected values are given in Table 1 (straight aluminium or copper<br />

conductors) and Table 2 (steel-cored aluminium conductors).<br />

Inductive Reactance ohms/km at 50 Hz and 1 metre spacings<br />

Conductor Reactance Conductor Reactance<br />

7 / 1.25 0.414 7 / 4.50 0.334<br />

7 / 1.75 0.393 7 / 4.75 0.330<br />

7 / 2.00 0.384 19 / 1.75 0.359<br />

7 / 2.25 0.377 19 / 2.00 0.350<br />

7 / 2.50 0.371 19 / 2.75 0.330<br />

7 / 2.75 0.365 19 / 3.00 0.325<br />

7 / 3.00 0.359 19 / 3.25 0.320<br />

7 / 3.50 0.350 19 / 3.75 0.311<br />

7 / 3.75 0.345 19 / 4.75 0.296<br />

Table 2. Non-Ferrous Conductors<br />

Inductive Reactance ohms/km at 50 Hz and 1 metre spacing<br />

Conductor Reactance Conductor Reactance<br />

6 / 1 / 1.25 0.372 30 / 7 / 2.50 0.315<br />

6 / 1 / 3.00 0.362 30 / 7 / 3.00 0.304<br />

6 / 1 / 3.75 0.346 30 / 7 / 3.50 0.294<br />

Table 3. Steel-cored aluminium conductors (ACSR/GZ and ACSR/AZ)<br />

36


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Separation mm<br />

0 25 50 75 100 125 150 175 200 225<br />

250 –0.087 –0.081 –0.076 –0.071 –0.066 –0.062 –0.058 –0.054 –0.050 –-0.047<br />

500 –0.044 –0.040 –0.038 –0.035 –0.032 –0.030 –0.027 –0.025 –0.022 –0.020<br />

750 –-0.018 –0.016 –0.014 –0.012 –0.010 –0.008 –0.007 –0.005 –0.003 –0.002<br />

1000 0 0.002 0.003 0.005 0.006 0.007 0.009 0.010 0.011 0.013<br />

Table 4. Correction factors<br />

Note the use of 1 metre as a standard spacing in the tables. In Table 3, correction values are<br />

shown which can be applied if the conductor spacing is not 1 metre.<br />

For example if the spacing was 525 mm, looking across the second row labelled ‘500’ to the<br />

column ‘25’, we see that the correction factor is –0.040.<br />

You can see that the reactance per unit length of an <strong>overhead</strong> line does not vary greatly with the<br />

spacing regardless of the conductor size.<br />

For instance, with a 19/2.75 (being a 112.9 square millimetre conductor) the reactance varies only<br />

between 0.286 ohms per km (0.330 - 0.044 = 0.286) at 0.5 metre spacing and 0.343 ohms per km<br />

(0.330 + 0.013 = 0.343) at 1.25 metre spacing.<br />

From a practical aspect, therefore, there is no appreciable error resulting if we assume a constant<br />

reactance value for any particular conductor size on the assumption that spacings for the line<br />

voltage will stay within a specific range.<br />

The graph in Figure 5 illustrates the relationship between resistance, reactance and impedance<br />

for conductors with various values of cross sectional area.<br />

From this we can see why there is little advantage to be gained by using conductors larger than<br />

112.9 square millimetres (19/2.75) to reduce voltage drop because of the impact of the line<br />

reactance.<br />

Underground cables also have inductance but as the conductors are much closer together than<br />

their <strong>overhead</strong> counterparts (because they are wrapped in insulation) their inductance is also<br />

somewhat lower.<br />

This means a smaller voltage drop for the same load and hence underground cables can transmit<br />

power further than a same-sized <strong>overhead</strong> line.<br />

ABC <strong>overhead</strong> conductors, because they are insulated, are also spaced closer together than bare<br />

conductors and likewise have a somewhat lower inductance, similar to that of underground<br />

cables.<br />

Covered conductors, with spacing between that of bare-wire <strong>overhead</strong> and underground cables,<br />

have a slightly lower inductance than bare-wire <strong>overhead</strong> but not as low as underground.<br />

Transformers at all voltages have inductance, which is caused by some of the magnetic field<br />

produced by the primary coils not linking completely with the secondary coil.<br />

This stray field, called ‘leakage flux’, has its own inductance which causes a voltage drop in the<br />

transformer.<br />

37


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Ohms per km<br />

1.1<br />

1.0<br />

0.9<br />

0.8<br />

0.7<br />

0.6<br />

0.5<br />

0.4<br />

0.3<br />

0.2<br />

0.1<br />

Impedance Z<br />

0<br />

0 25 50 75 100 125<br />

Cross section – sq mm<br />

REACTANCE BASED ON 3 PHASE<br />

EQUALLY SPACED FLAT CONSTRUCTION<br />

WITH CONDUCTORS 775 MM APART<br />

Figure 5. Relationship between resistance, reactance and impedance for conductors of differing<br />

cross-sectional areas<br />

38<br />

Reactance X<br />

Resistance R<br />

150<br />

175<br />

200


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Shunt capacitance<br />

Underground cables and long lines at high voltages also have shunt capacitance between<br />

conductors and between conductors and ground.<br />

This is because conductors running parallel to one another behave a little like the plates on a<br />

capacitor.<br />

Capacitance helps to counteract the effect of inductance in feeders, reducing the voltage drop at<br />

full load. it may cause problems at light load, causing the voltage to rise along the line to<br />

unacceptably high levels.<br />

Capacitance is rarely an issue for <strong>distribution</strong> lines and typically is only considered for long<br />

transmission lines at voltages of 132kV and above.<br />

Revision exercise 7<br />

1. What three factors combine to determine the value of the impedance of<br />

<strong>distribution</strong>/transmission lines?<br />

2. What are the factors that influence the inductance of <strong>overhead</strong> lines? Why is<br />

inductance a problem?<br />

39


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Equipment used in the control of voltage<br />

Introduction<br />

There are three general methods used to control the voltage at the end of a <strong>distribution</strong> feeder.<br />

They are by using:<br />

• control equipment to vary the voltage at the supply end of the feeder<br />

• control equipment at the load end which can vary the voltage<br />

• controlling the current in the line by changing the power factor.<br />

At the transmission source, voltage is controlled by the voltage regulators on the generators.<br />

Voltage control equipment connected at either the supply end or the load end of the feeder would<br />

include off-load tap changing transformers, on-load tap-changing transformers, booster<br />

transformers, moving coil regulators, induction regulators.<br />

Current controlling devices intended to control the power factor are either static or rotary<br />

capacitors.<br />

Rotary capacitors are rarely if ever used in modem power <strong>systems</strong> and will not be discussed.<br />

Voltage changing equipment<br />

Tap-changing transformers are constructed so that the output voltage can be adjusted by means<br />

of a switch to increase or decrease the voltage.<br />

Details of how this is done are given in the subject Power Transformers.<br />

The switches can be designed to either carry no current at the time the voltage value is changed<br />

(off-load tap-changer) or to carry the full rated current (on-load tap-changer).<br />

Usually the voltage is changed in increments of the rated voltage – typically 2.5% for <strong>distribution</strong><br />

(22/11 kV to 400 volt) transformers but finer, say 1.25 – 1.5% for transformers in transmission<br />

substations- with a full range of adjustment up to ±10% of the rated output voltage.<br />

This means that for an 11 kV line the voltage at the supply end can be between 9.9 kV and<br />

12.1kV.<br />

On-load tap-changers ensure there is no interruption to the electricity supply during the change of<br />

voltage value, and as a consequence are preferred, even though they are much more expensive.<br />

When off-load tap-changers are installed the electricity supply must be disconnected for the<br />

duration of time required to change the voltage setting.<br />

Typically, zone and transmission substation transformers are fitted with on-load tap changers<br />

because of the very high numbers of customers which would be affected if they had to be<br />

disconnected each time a tap change had to be made.<br />

The essential elements of the load and the compensating circuits used for the automatic control of<br />

an on-load tap- changer are shown in Figure 6.<br />

Essentially it consists of a voltage sensing relay, which will actuate the tap-changer motor to<br />

move the tap position automatically up or down as the voltage varies away from the set desired<br />

voltage level.<br />

This set level is usually referred to as the ‘float voltage’ of the transformer or substation.<br />

40


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Figure 6(a). Load and Control Circuits<br />

Main Circuit Control Circuit<br />

ES Sending end voltage eT Voltage transformer output voltage<br />

EZ Line voltage drop eC Compensator voltage drop<br />

ER Receiving end voltage eV Regulating relay voltage<br />

RL Line resistance RC Compensator resistance<br />

XL Line reactance XC Compensator reactance<br />

IL Load current iC C.T. secondary current<br />

Figure 6(b). Phasor diagrams of load and control circuits<br />

The voltage relay senses both transformer output voltage, plus a compensating voltage which<br />

reflects the drop expected in the feeder, as below.<br />

To understand how the system works, firstly consider the simplest case, where the transformer<br />

output voltage drives the relay.<br />

The output of the transformer is measured by the voltage transformer. If the output voltage falls<br />

outside the set level (‘float voltage’) due to say increasing load, the voltage regulating relay will<br />

activate the tap-changer and change one tap position on the transformer, to raise the voltage and<br />

bring the output voltage back to its desired level. Conversely, as load falls off, the output voltage<br />

will start to rise and the voltage regulating relay will cause the transformer to change one tap back<br />

to lower the voltage and again bring it back to the desired level.<br />

We can also compensate for the drop in the feeders going out from the substation by circulating<br />

the output of the current transformer through adjustable resistance and reactance values (which<br />

are set to reflect the resistance and reactance values of the feeder) in the voltage sensing circuit.<br />

The drop in the model impedance ZC in the voltage regulating relay should be able to reflect the<br />

drop in voltage in the feeder, if properly set up.<br />

41


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

The voltage sensing relay would now cause the transformer to change taps in response to<br />

variations in the voltage at the load at the end of the feeder, rather than just at the terminals of the<br />

transformers at the substation.<br />

When the load is increasing, this would mean taps would change earlier than by sensing<br />

transformer output voltage alone and the transformer output voltage would be higher, but at the<br />

load end of the feeder the voltage would be kept at the desired level.<br />

This can be seen in the phasor diagram in Figure 6.<br />

The voltage transformer output et is a reflection of ES, the zone transformer terminal voltage.<br />

By subtracting from the voltage phasor et a voltage phasor ez which is proportional to the line<br />

voltage drop EZ, the resultant voltage ev (which controls the driving mechanism of the tapchanger)<br />

will represent the load voltage ER for all conditions.<br />

This compensation for the voltage drop in the line is called ‘line drop compensation’ (‘LDC’). It is<br />

usually set as a percent boost in voltage at a certain value of transformer load.<br />

In summary, if the LDC is zero, the transformer voltage regulation relay will change taps purely on<br />

transformer terminal voltage.<br />

When the LDC is set at some positive value, the transformer voltage regulation relay will change<br />

taps based on the transformer terminal voltage less the line drop voltage value.<br />

Types of voltage regulators<br />

Regulators<br />

The simplest and most commonly used method of boosting voltage on <strong>distribution</strong> lines by far,<br />

where capacity is not an issue, but where voltage variation is excessive (eg rural feeders) is via<br />

an auto transformer, usually simply (but not accurately) referred to as a ‘voltage regulator’<br />

(because as we will discuss below, there are many types of regulators).<br />

An auto transformer has one common coil instead of separate primary and secondary coils as<br />

with traditional transformers.<br />

Output voltage can be boosted by having more turns on the output tap or reduced (‘bucked’) by<br />

having less turns on the output tap position, as shown in Figure 7.<br />

Figure 7. Voltage Regulator (Auto-transformer)<br />

42


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Taps are automatically changed by an on-load tap changer described above.<br />

Another device for controlling voltage which may be used by itself or in conjunction with a<br />

transformer is a regulator, of which there are two types:<br />

• induction regulators<br />

• moving coil regulators.<br />

An induction regulator consists of a stator and rotor, and is constructed in a similar manner to a<br />

wound rotor induction motor with flexible connections coming from the rotor which does not rotate.<br />

The angular position of the (stationary) shaft relative to the stator casing is controllable by means<br />

of a manually or motor driven geared wheel.<br />

One winding (the stator) is shunt connected across the lines which need their voltage to be<br />

controlled, whilst the other winding (the rotor) is connected in series with the load or <strong>overhead</strong><br />

line.<br />

Depending on the relative angular positions of the stator and the rotor, the shunt winding induces<br />

a voltage (v1) into the series winding, where the induced voltage may be in phase with the system<br />

voltage or may be up to 1800 out of phase.<br />

The result is that the output voltage can be varied in magnitude between the range:<br />

(V + v1) to (V – v1)<br />

where: V is the input voltage<br />

v1 is the injected series voltage<br />

The normal three phase arrangement has the disadvantage that it introduces a phase shift<br />

between the input and output voltages at all values except full boost and full buck.<br />

This is of no consequence when used on an individual supply, but precludes its use on<br />

interconnected networks.<br />

A moving coil regulator is constructed with two pairs of closely coupled shunt and series coils<br />

A1 - S1 and A2 – S2 respectively as shown in Figure 8.<br />

Figure 8. Circuitry of a moving-coil regulator<br />

43


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

The four coils are mounted on a common magnetic circuit, and a moving coil M is placed over the<br />

top of them.<br />

The moving coil M is short circuited onto itself, and at its limits of travel surrounds one or other of<br />

the pairs of fixed coils.<br />

The shunt coils A1 and A2 are connected with their voltage polarity additive and the series coils S1<br />

and S2 have their voltages in opposition.<br />

The mutual inductance of the short circuited coil M when in the top position, reduces the voltage<br />

across A1 to a minimum and increases that across A2 to a maximum.<br />

In this case, the voltage induced into S1 is a minimum and that in S2 is a maximum.<br />

The range of control on the output voltage depends on the ratios of S2:A2 and S1:A1.<br />

Boosters<br />

Another less common technique for making small adjustments to line voltages uses line booster<br />

transformers.<br />

There are two type of arrangements:<br />

• in phase booster transformers<br />

• quadrature booster transformers.<br />

An in phase regulating booster transformer is used to inject a variable voltage into a line circuit for<br />

voltage regulating purposes.<br />

This equipment would be used where it is desirable to obtain additional voltage control on the<br />

lines when loaded, and there is no wish to purchase a new transformer.<br />

A typical winding arrangement for an in phase booster is shown in Figure 9.<br />

The active conductors of the three phase system are indicated by AA’, BB’, CC’ respectively, and<br />

the relevant voltage levels are shown on the phasor diagram.<br />

Figure 9. Winding arrangement of a separate in-phase voltage regulating booster transformer<br />

44


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Three series transformers ‘a’ have their secondary windings ‘b’ connected into the lines A-A’,<br />

B-B’, C-C’.<br />

The primary windings of these transformers ‘c’ are excited from the variable outputs of the three<br />

phase transformer ‘e’ whose primary windings are connected across the line ABC in star<br />

configuration.<br />

Variation of the tap-changer ‘x’ between the terminals ‘d to f’ will change the voltage injected into<br />

the line A-A’, B-B’, C-C’ through the transformers ‘a’.<br />

Quadrature boosters, or phase angle control units inject a voltage having a major component at<br />

90 0 electrical to the existing line voltage.<br />

This is achieved by combining voltages from different phases instead of the same phase. A<br />

general method of interconnection is shown in Figure 10.<br />

They are essentially a variation of the in-phase booster described above.<br />

Figure 10. Winding arrangement of phase-angle displacement transformer – quadrature booster<br />

By moving the tap-changer mechanism ‘x’ from terminal ‘g’ to ‘f’ the line voltage will be increased<br />

(‘boost’) and when going from ‘g’ to ‘d’ the line voltage will be reduced (‘buck’).<br />

Phase angle control equipment may be required when two circuits of different impedances<br />

carrying variable loads are connected at two points on the system.<br />

Starting at the point where the lines have their ends connected together and with the other ends<br />

of the lines disconnected, the different line impedances means that there will be a phase<br />

difference between the two voltages at the other ends of the lines when they each carry a current.<br />

This phase displacement will vary as the loads on the two feeder lines vary. When the two feeder<br />

lines are connected into the system the difference in voltages due to the phase displacement at<br />

their ends will cause a circulating current to flow.<br />

45


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

When a quadrature booster is used at the end of one of these lines it is possible to change the<br />

<strong>distribution</strong> of current in the feeders and minimise any circulating currents.<br />

Power factor correction<br />

While voltage control by means of tap changing transformers is the usual method in <strong>distribution</strong><br />

<strong>systems</strong>, power factor correcting capacitors can also have an effect on regulating voltages.<br />

The phasor diagram Figure 11 illustrates the effects on voltage regulation by adding capacitors to<br />

a load and so changing the power factor.<br />

The values of voltage supplied without capacitors connected is shown in full lines (ES) and with<br />

capacitors, which reduces the angle of current lag from Φ to Φ1, in dashed lines (ES1).<br />

Note how ES1 is smaller than ES, ie the voltage regulation is less.<br />

Figure 11. Voltage phasor diagram<br />

For the voltages before the capacitors are connected:<br />

OI = load current at uncorrected phase angle<br />

OER = receiving voltage or load voltage<br />

ERES = line voltage drop due to line current I<br />

OES = sending end voltage<br />

When the capacitors are connected the ‘in phase’ component of load current I remains the same,<br />

but the quadrature component is reduced resulting in a new load current I. Assuming that the load<br />

voltage ER remains constant, then:<br />

OI1 = load current at corrected phase angle<br />

OER = receiving voltage or load voltage<br />

ERES1 = line voltage drop due to line current I1<br />

OES1 = new sending end voltage<br />

It can be seen that the phasor OES1 is less than OES, and so a lower voltage is required at the<br />

sending end to keep the load voltage constant. Normal practice is to keep the sending end<br />

voltage constant and to switch capacitors in and out at the receiving end to adjust the receiving<br />

end voltage.<br />

46


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Revision exercise 8<br />

1. Name the devices which control voltages in transformers.<br />

2. Describe briefly what is meant by ‘line drop compensation’. How does it work?<br />

3. List different types of voltage regulators.<br />

4. Explain what is meant by power factor correction and how it assists the <strong>distribution</strong><br />

system.<br />

47


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Voltage profiles<br />

Voltage profile charts are useful for studying patterns and locating causes or reasons for<br />

abnormal voltage conditions.<br />

Put simply, a voltage profile is a chart which shows how the voltage varies as you travel out from<br />

the source of supply to the customers.<br />

To obtain the complete variation of voltage, one would need to draw two profiles—one for full load<br />

conditions, giving minimum volts at the customer, and one for no-load or light load, giving<br />

maximum volts at the customer.<br />

The chart will show all the voltage drops in the various elements which make up the <strong>distribution</strong><br />

feeder, eg:<br />

a) The supply voltage at the zone substation<br />

b) The voltage drop in the 11/22 kV feeder<br />

c) The voltage drop in the <strong>distribution</strong> transformer<br />

d) The voltage drop in the low voltage feeder running from the <strong>distribution</strong> transformer to the<br />

take-off point to the customer’s terminals<br />

e) The voltage drop in the customer’s service line, ie from the take-off point to the ‘customer’s<br />

terminals’.<br />

To make a chart, a common or reference voltage level is selected for the system and the circuit<br />

constants of resistance, reactance, etc. are converted to their effective values at this voltage by<br />

means of the formula:<br />

⎛ E<br />

⎞<br />

R<br />

⎠<br />

2<br />

R2 E ⎟<br />

1<br />

⎟ = ⎜<br />

⎝<br />

1<br />

where: R2 = resistance value effective at reference voltage E2<br />

R1 = resistance value effective at operating voltage E1<br />

48


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Some practical examples<br />

1. Figure 12 shows a simple <strong>distribution</strong> system for a single consumer represented by a<br />

single line diagram with the voltage profile for full load conditions using a 415 volts base.<br />

Figure 12. Simplified single line diagram of a <strong>distribution</strong> system with voltage profile for full-load<br />

conditions.<br />

Here, we see the components of the voltage drop as we go outwards from the substation down<br />

the feeder to the customer.<br />

2. If we now consider a <strong>distribution</strong> system for the supply of four consumers a simplified<br />

single line diagram could be as shown in Figure 13.<br />

Figure 13. Simplified single line diagram of a <strong>distribution</strong> system for the supply of four customers.<br />

In this situation we are seeking to keep the voltage to all customers within the range ±6% of the<br />

nominal voltage.<br />

Of the four customers, A and B are on <strong>distribution</strong> transformer T1 close to the zone substation,<br />

whilst C and D are on <strong>distribution</strong> transformer T2 remote from the zone substation. Customers A<br />

and C are close to their respective transformers and customers B and D are remote from their<br />

respective transformers.<br />

49


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

The V values indicated on Figure 13 show the percentage impedance voltage drop per unit for<br />

each customer’s full load current.<br />

For example, if all customers take full load currents the voltage drop on feeder A = 1%, the<br />

voltage drop in T1 = 4% because of the two units of full load current, and the voltage drop in the<br />

high voltage feeder = 4% because of the two units of full load current taken by C and D. The light<br />

load conditions are taken as being 25% of full load current.<br />

Figure 14. Voltage profile for light and heavy loads - zone transformer with on load tap changer<br />

Figure 15. Voltage profile for light and heavy loads - zone transformer with on load tap changer,<br />

<strong>distribution</strong> transformer with off load tap changer<br />

50


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Considering Figure 14, this indicates the voltage variations resulting from where the zone<br />

substation tap changer can vary the voltage but the <strong>distribution</strong> transformers are of fixed ratio.<br />

This is the typical arrangement in most power <strong>distribution</strong> <strong>systems</strong>.<br />

For a light load the zone transformer tap changer is set at 100%, and for full load the zone<br />

transformer might be adjusted to give 10% boost in voltage to compensate for the voltage drop in<br />

the feeder, ie the LDC boost is set at 10%.<br />

At full load with 10% voltage boost, the voltage at D is –6% and the voltage at A is +5%. For light<br />

load, with the zone transformer at 100%, the voltage at D is –4% and at the voltage at A is –1.5%.<br />

3. Considering Figure 15, this indicates the voltages resulting from a situation where the<br />

zone substation tap changer can vary the voltage and the <strong>distribution</strong> transformer T2 can<br />

provide a 2.5% boost using an off load tap changer. Again, for a light load the zone<br />

transformer tap changer is set at 100%, and for full load the zone transformer is adjusted<br />

to give 10% boost.<br />

At full load with 10% voltage boost, the voltage at D is –3.5% and the voltage at A is +5%. For<br />

light load, with the zone transformer at 100%, the voltage at D is –1.5% and at the voltage at A is<br />

–1%.<br />

Diagrams of this type show fairly simply the effects of changing the tap settings on zone and<br />

<strong>distribution</strong> transformers. In contemporary practice, the voltage drop calculations are done quickly<br />

and easily on computers.<br />

Revision exercise 9<br />

1. Describe briefly what a ‘voltage profile’ is. Where might you use one?<br />

51


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

2. What is meant by the voltage regulation of a feeder? Express this as an equation.<br />

3. Name the causes of voltage regulation in a <strong>distribution</strong> feeder.<br />

4. What is meant by the inductance of <strong>overhead</strong> lines? What factors influence the inductance<br />

of a line?<br />

5. Name a major advantage that underground cables and ABC <strong>systems</strong> have in terms of<br />

inductance.<br />

52


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Wires and Cables<br />

The qualities desired in electric-service wires, in so far as the construction is concerned, are<br />

mechanical strength, tenacity, and ability to resist corrosion or other deterioration. In ordinary<br />

practice the breaking strength required for a wire of a given span will depend entirely on the sag,<br />

because increasing the sag will reduce the wire tension approximately in proportion to the sag.<br />

Practical considerations, however, indicate a rather indefinite minimum, below which it is<br />

undesirable to go. Any surface injury, such as local pitting by arcs and nicks caused by careless<br />

handling, or any weakness in the material due to errors in manufacture, will have relatively greater<br />

effect on a small wire than on a large one. Moreover, such faults are more serious in solid wires<br />

than in stranded cables and in hard-drawn wire than in soft-drawn wire. In stranded cables, an<br />

injury to a single strand affects only a fractional part of the entire section; in hard-drawn wire the<br />

surface, or skin material, has approximately twice the unit strength of the interior mass, so that an<br />

injury will have a relatively greater effect on hard-drawn wire.<br />

Fortunately, however, the process of wire drawing insures a large amount of work per unit of<br />

mass, so that the finished product is a very homogeneous and trustworthy material. This quality,<br />

combined with the reduction in stress resulting from any increase in sag caused by stretching,<br />

explains the comparative immunity from mechanical failures.<br />

Copper<br />

The good qualities of copper wire are a matter of common knowledge, and as stated previously,<br />

its manufacture and method of use combine to make it almost unique as a material of<br />

construction. It is fairly immune from corrosive action, as ordinarily used in transmission-line work,<br />

although it is not absolutely indestructible. The principal sources of injury to copper are due to its<br />

softness and low melting point. The former renders it liable to nicks or broken strands in stringing<br />

and clamping, and the latter to burning by arcs.<br />

Unless the voltage is such that insulated or weatherproof wire affords some real protection, there<br />

is no logical structural reason for using it. Otherwise, it merely serves as an additional load and<br />

offers a greater diameter for sleet deposits, besides deteriorating far in advance of the rest of the<br />

construction and frequently hanging in unsightly streamers.<br />

Since the sheen of freshly strung copper is greatly lessened after exposure, it becomes<br />

problematical whether the attention of the casual observer would in reality be attracted more by<br />

the copper or by the size and spacing of insulators which cannot be disguised.<br />

Copper Covered<br />

A comparatively recent development in transmission-line wires is the use of a steel wire covered<br />

with copper. This product is produced by drawing out an ingot of steel which has been previously<br />

encased in a copper covering.<br />

The thickness of the shell of copper may be varied within wide limits, the usual commercial<br />

proportions being an amount of copper that, combined with the lower conductivity of the steel<br />

core, produces a wire having either 30 or 40 percent of the conductivity of a copper wire of the<br />

combined gage. Thirty percent copper-covered wire is about 5 percent stronger than 40 percent<br />

wire of the same gage. The thickness of the shell of copper is quite small, depending in part on<br />

the size of the wire.<br />

Such wire should, therefore, be handled at least as carefully as copper wire. Since the thickness<br />

of the copper decreases with the size of the wires in the cable, it is preferable, at least for<br />

<strong>overhead</strong> ground wires, to use the 40 percent grade or else to use cables of few strands.<br />

53


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

The steel from which the wire is drawn is a high-carbon steel having an ultimate strength of about<br />

90,000 lb. per square inch, and a correspondingly high elastic limit. During the process of copper<br />

coating and wire drawing, there is an annealing effect followed by hardening, the net result being<br />

to produce a wire having an ultimate strength not greatly below that of the original ingot material.<br />

In general, and with the grade of steel commonly used by manufacturing companies, the ultimate<br />

strength of copper-covered wire is from 20 percent to 40 percent greater than that of the<br />

corresponding sizes of hard-drawn copper.<br />

The principal uses of this material in transmission work are for <strong>overhead</strong> ground wires, telephone<br />

wires, and the power wires of the lighter and lower capacity lines, where little future growth of<br />

business may be expected.<br />

Aluminium<br />

Aluminium wire, as now used for power-line purposes, is usually employed in the form of<br />

stranded cables, and when so used is no longer subject to some of the troubles incident to the<br />

earlier installations. As a material, it is quite different from copper, although used for similar<br />

purposes. Therefore, in making price comparisons, it is necessary to consider not only the price<br />

per mile per unit of electrical rating, but also the changes in the general construction of the line.<br />

The conductivity of aluminium is about 60 percent, based on the Matthiesen standard for copper,<br />

making aluminium cables about 1.5 times the area and 1.25 times the diameter of copper cables<br />

having equal conductivity. As the specific weight of aluminium is about 0.33 that of copper, the<br />

weight of aluminium cable will be about 0.5 times that of copper cable having the same<br />

conductivity.<br />

The strength of aluminium is about 0.8 that of soft copper and 0.4 the strength of hard copper.<br />

The net result of these differences is best shown by a concrete example. Thus, a No.00<br />

aluminium cable has about the same conductivity as a No.1 stranded hard-drawn copper cable,<br />

and their other characteristics for a 400 foot span are as follows:<br />

Since the coefficient of expansion of aluminium is considerably higher than that of copper,<br />

aluminium cables are more affected by temperature changes. Relatively greater sags will<br />

therefore occur in hot weather, while at low temperatures there is a greater increase in tension<br />

due to the contraction of the material with its resultant decrease in sag. In addition, the lighter<br />

weight of aluminium renders it more liable to local displacement by wind pressure. It is necessary,<br />

as a result of these differences in the material, to provide greater pin separation and <strong>overhead</strong><br />

clearance for aluminium conductors. From a construction viewpoint, however, the lighter weight of<br />

54


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

aluminium does not possess any particular merit, except possibly greater ease of handling the<br />

reels and pulling out wire in stringing.<br />

The saving in dead load on the supports is negligible and is more than offset by the greater sag<br />

and separation required. Furthermore, the increased diameter imposes a greater wind load. The<br />

choice between aluminium and copper will depend on the relative cost of the two materials and<br />

their accompanying construction, together with the allowances which can be made for the scrap<br />

values of the two installations.<br />

Steel<br />

Steel cable can be obtained of almost any desired unit breaking strength, the commercial grades<br />

ranging from the low grade steel of guy wire, which has an ultimate strength of 60,000 lb. per<br />

square inch, to steels of 200,000 lb. or more.<br />

For transmission-line purposes steel cable is used chiefly for <strong>overhead</strong> ground wires or as power<br />

wires for very long spans. The occasional use of steel messengers for telephone or insulated<br />

cables does not involve any considerable quantity of such material employed on typical<br />

transmission lines.<br />

Steel cables for line work should always be galvanized, and should be larger than is actually<br />

required for strength. The galvanizing of cable is by no means as permanent a protection as the<br />

hot-dip, unwiped process applied to structural steel; therefore some allowance should be made<br />

for future corrosion.<br />

Despite the temptation to use small-gage cables made of the higher grade steels, on account of<br />

their greater strength, it is generally preferable to adhere to medium grades such as the Siemens-<br />

Martin. Guy-strand steel cable is the lowest commercial grade and its quality is relatively much<br />

lower than that of any of the higher grades, Large diameter cables, particularly of high-grade<br />

steel, are rather difficult to handle as they are very stiff. It should be noted that all cables of great<br />

strength require special clamping attachments for dead ending, the ordinary quota of clips and<br />

clamps being inadequate to transmit the tension.<br />

Telephone Wire<br />

Supporting a telephone circuit on long-span transmission-line structures introduces a difficulty, in<br />

that the small wires which are sufficient for telephone service do not have the mechanical strength<br />

to carry safely in long spans.<br />

It is almost impossible to string any ordinary telephone wires so that they will be reasonably<br />

secure on long-span lines. There have arisen, therefore, two general methods of procedure; one<br />

is to use larger and stronger wires; and the other to contemplate failure in the telephone circuit as<br />

a necessary evil.<br />

Solid steel wire No.6 BWG, sometimes called river crossing wire, has an ultimate strength about<br />

equal to that of No.00 stranded hard-drawn copper and can, therefore, be strung equally well in<br />

long-span lines.<br />

Catenary<br />

If two ends of an imaginary wire having perfect flexibility and uniformity of material but no ductility<br />

were supported at two points in the same horizontal plane the wire would take the shape of a<br />

curve known as the catenary. For all practical purposes it may be assumed that actual wires and<br />

cables possess the same characteristics. The curve of the wires between the supports is<br />

therefore known, if the span and sag are known. However, as the equation of the catenary is<br />

rather complicated, while that of the parabola, which closely resembles it, is simple, the latter is<br />

usually employed instead; thus,<br />

y²= ax<br />

"a" being an constant found by substituting the known value of sc for the point on the curve at the<br />

support, ie.,<br />

a = in which S is the length of the span and d is the sag<br />

55


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Assume a uniform load on each lineal foot of the span, and imagine half of the span removed and<br />

the wire held in place by the tension T at the middle of the span. Then considering the moments<br />

about the remaining support we have the weight of the half span multiplied by its lever arm which<br />

is one-quarter of the span, equals the balancing force T multiplied by its lever arm d.<br />

Since the total weight W = the weight per foot, X the half span or W = we have<br />

X = Td<br />

Therefore = Td<br />

and T =<br />

or, the tension in the wire equals the weight per foot times the span squared divided by eight<br />

times the sag.<br />

It is necessary, however, to take into consideration the effect of a change in length of the wire due<br />

to temperature and loading, and a simple arrangement of formula in which this is done is given<br />

below. The following mathematical treatment is not new, but the writer has found the arrangement<br />

convenient:<br />

S = span, in feet.<br />

d = sag, in feet.<br />

W = load per lineal foot in plane of wire.<br />

A = area of wire, in square inches. .<br />

E = modulus of elasticity.<br />

0 = coefficient of expansion.<br />

t = change of temperature, in degrees.<br />

e = elongation or change of length, within elastic limit.<br />

L₀ = length, in feet, of imaginary wire (W = 0) at normal temperature.<br />

Loc = length, in feet, of imaginary wire, cold (t°F. below normal temperature).<br />

= length, in feet, of imaginary wire, hot (t°F. above normal temperature).<br />

Loh<br />

Index to Subscripts. -<br />

No subscript = normal conditions.<br />

c = cold: t°F. below normal + dead load.<br />

i = cold: ice load + dead load.<br />

cw = cold: wind load + dead load.<br />

iw = cold: ice + wind + dead load.<br />

h = hot: t°F. above normal + dead load.<br />

W iw is the resultant of the vertical dead + ice loads and the horizontal wind load.<br />

W cw is the resultant of the vertical dead load and the horizontal wind load.<br />

56


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Stresses<br />

Substitute normal values in Eqs. 1, 2, 3, and 4. Assume values of Th, Tiw, Tc, Ti, or Tcw, such that<br />

Eqs. 5 and 6 will give identical values of dh, diw, etc. The tension that will give the same sag by<br />

Eqs. 5 and 6 (independently) is the tension resulting from that sag and the given loading.<br />

T = (1)<br />

L = S (2)<br />

e = (3)<br />

Lo = L – e (4)<br />

(t°. above normal, with dead load.)<br />

Loh = Lo (1 + 0 th) en = Lh = Loh + en<br />

dh = 0.612 (5)<br />

dh = (6)<br />

(t°. below normal, with dead + ice + wind loads.)<br />

Loc = Lo(1 – 0tc) eiw = Liw = Loc + eiw<br />

diw = 0.612 (5)<br />

diw = (6)<br />

(t°F. below normal, with dead load.)<br />

Loc = Lo(1 – 0tc) ec = Lc = Loc + ec<br />

dc = 0.612 (5)<br />

dc = (6)<br />

(t°F. below normal, with dead + ice loads.)<br />

Loc = Lo(1 – 0tc) ei = Li = Loc + ei<br />

di = 0.612 (5)<br />

di = (6)<br />

(t°F. below normal, with dead + wind loads.)<br />

Loc = Lo (1 – 0tc) ecw = Lcw = Loc + ecw<br />

dcw = 0.612 (5)<br />

dcw = (6)<br />

In Tables 1 to 8 are given the physical properties and the wind and ice loads for various wire<br />

gages.<br />

57


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Table 1 – Properties of Wire Material<br />

It has been urged by some that using the 0.5 inch, ice and 8-lb. wind load with the parabolic<br />

formula for computing the stress in the wire docs not give results which accord with experience,<br />

since actual spans erected with less than the specified sags have not failed in service.<br />

On the other hand, it is sometimes claimed that allowing maximum stresses near the elastic limit<br />

is dangerous. The facts of the matter are:<br />

First, the true catenary formula is scientifically and mathematically correct within the elastic limit.<br />

Second, the parabolic formula, ordinarily used for simplicity, gives results which in the vast<br />

majority of cases are closer to the exact values than the actual wire stringing will be to the<br />

specified stringing.<br />

Third, the material of a wire catenary is more uniform in section, strength, and other<br />

characteristics than that of any other engineering structure; therefore the error of design is<br />

correspondingly less.<br />

Fourth, the stretch of a ductile material, such as copper, permits the sag to increase and the<br />

stress to decrease and, within limits, does not perceptibly decrease the cross-section at any point.<br />

Therefore, a loaded span stretches enough to relieve the stress and docs not fail unless the load<br />

is very excessive.<br />

Fifth, the specified maximum loading is an emergency loading and is not a general or frequent<br />

occurrence on any span or line.<br />

¹ The elastic limit used is in reality the yield point, or point of appreciable extension, as this value seems more<br />

applicable to wire stringing than that obtained by accurate laboratory tests.<br />

The facts of the matter are that the spans in service have either not been subjected to loads in<br />

excess of those required by the catenary formula to develop their elastic limit, or the wire has<br />

stretched and the sag has increased.<br />

Possibly there are two other reasons for seemingly overstressed lines giving satisfactory service.<br />

One is that the poles have bent or the wires slipped through the ties, thus temporarily increasing<br />

the sag.<br />

Second, the wires may have become tempered or hardened by tension, possibly by atmospheric<br />

changes or other action, and by becoming harder have been able to sustain a greater load.<br />

58


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

59<br />

Figure 1 Sags and Tension of No. 1 H.D.<br />

Copper<br />

Figure 2 Sags and tensions of No. 0<br />

H.D.Copper


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Figure 3 Sags and Tensions on No. 00 H.D. Copper<br />

60


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Table 2 Properties of Bare Stranded Copper Cable<br />

61


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Table3 properties of solid copper<br />

62


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Table 4 Properties of Stranded Aluminium Cable<br />

63


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Table 5 Table 6<br />

64


DESIGN OVERHEAD DISTRIBUTION SYSTEMS<br />

Figure 4 Normal Sags, copper wires and cables Figure 5 Normal Sags, Aluminium Cables<br />

Table 7 Properties of Wire Material<br />

65

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!