Section 3

DESCRIPTION

3.1General Description

3.1.1Refrigeration Unit - Front Section

The unit is designed for the majority of components to be accessible from the front (see Figure 3.1). The unit model number, serial number, and parts identification number can be found on the nameplate left of the compressor.

3.1.2Fresh Air Makeup Vent

The function of the upper or lower makeup air vent is to provide ventilation for commodities that require fresh air circulation. A manually operated venting system is located in the upper left access panel.

The optional eAutoFresh vent system is to moderate the atmospheric level in the container in response to cargo respiration. When transporting frozen cargo loads the vent will be closed. The upper left access panel contains the vent slide and motor assembly. It may be removed to allow entry into the evaporator section where the CO2 sensor and drive pack are located.

Figure 3.1  Refrigeration Unit − Front Section

Fig-Refrig-Unit-Front.jpg 

1.Access Panel (Evap Fan #1) / TXV / HTT)

2.Fork Lift Pockets

3.Control Box

4.Compressor

5.Unit Serial Number, Model Number, and Parts Identification Number (PID) Plate

6.Condenser Fan

7.TransFRESH Communications Connector

8.Interrogator Connector (Front Left)

9.Temperature Recorder

10.Lower Fresh Air Makeup Vent Location (Blank Cover Shown)

11.TIR (Transports Internationaux Routiers) Sealing Provisions - Typical All Panels

12.Upper Fresh Air Makeup Vent or eAutoFresh (Automatic Vent) panel

13.Access Panel (Evaporator Fan #2) / Humidity Sensor / Return Temperature Sensor

- - - - -

3.1.3Evaporator Section

The evaporator section (Figure 3.2) contains the return temperature sensor, humidity sensor, thermostatic expan­sion valve, dual-speed evaporator fans (EM1 and EM2), evaporator coil and heaters, defrost temperature sensor, heat termination thermostat, and heat exchanger.

The evaporator fans circulate air through the container by pulling it in the top of the unit, directing it through the evaporator coil where it is heated or cooled, and discharging it at the bottom.

The evaporator components are accessible by removing the upper rear panel (as shown in Figure 3.2 below).

Figure 3.2  Evaporator Section − Units with Center Access Panel

Fig-Evap-Section.jpg 

1.Evaporator Fan Motor #1

2.Return Recorder Sensor (RRS) / Return Tempera­ture Sensor (RTS)

3.Humidity Sensor

4.Evaporator Fan Motor #2

5.Defrost Temperature Sensor (DTS)

6.Heater Termination Thermostat (HTT)

7.Evaporator Coil

8.Hermetic Thermostatic Expansion Valve

9.Heat Exchanger

10.Interrogator Connector (Rear) (ICR)

11.USDA Probe Receptacle PR2

12.USDA Probe Receptacle PR1

13.USDA Probe Receptacle PR3

14.Cargo Probe Receptacle PR4

15.Evaporator Coil Heaters

16.TXV Bulb Routing

- - - - -

3.1.4Compressor Section

The compressor section includes the compressor (with high pressure switch), power cable storage compartment, and autotransformer.

This section also contains the suction modulating valve, discharge pressure regulating valve, discharge tempera­ture sensor, and discharge/suction pressure transducers.

The supply temperature sensor, supply recorder sensor, and ambient sensor are located at the right side of the compressor.

Figure 3.3  Compressor Section

Fig-Compressor-Section.jpg 

1.Autotransformer

2.Power Cables and Plug

3.Compressor Sight Glass View Port

4.Compressor Guard

5.Supply Temperature Sensor (STS)

6.Supply Recorder Sensor

7.Ambient Sensor

8.Supply Air Thermometer Port

9.Discharge Service Valve

10.Discharge Temperature Sensor

11.Discharge Pressure Regulating Valve

12.Suction Temperature Sensor

13.Quench Valve Temperature Bulb

14.Quench Valve

15.Access Port

16.Suction Modulating Valve

17.Suction Service Valve

18.Compressor Crankcase Heater

19.Compressor Motor

20.Suction Pressure Transducer

21.Discharge Pressure Transducer

22.High Pressure Switch

- - - - -

3.1.5Air-Cooled Condenser Section

The air-cooled condenser section (Figure 3.4) consists of the condenser fan, condenser coil, receiver with sight glass/moisture indicator, quench valve, liquid line service valve, filter-drier, condenser pressure transducer, and fusible plug.

The condenser fan pulls air in through the bottom of the coil and discharges it horizontally out through the condenser fan grille.

Figure 3.4  Condenser Section

fig-condensor-section.jpg 

1.Grille and Venturi Assembly

2.Condenser Fan

3.Key

4.Condenser Fan Motor

5.Condenser Coil Cover

6.Condenser Coil

7.Condenser Motor Mounting Bracket

8.Receiver

9.Sight Glass

10.Fusible Plug (Rupture Disc - Alternate)

11.Condenser Pressure Transducer

12.Sight Glass/Moisture Indicator

13.Filter-Drier

14.Liquid Line Service Valve

15.Quench Valve

- - - - -

3.1.6Water-Cooled Condenser Section

The water-cooled condenser section (Figure 3.5) consists of a water-cooled condenser, sight glass, quench expansion valve, rupture disc, condenser pressure transducer, filter-drier, water couplings, and water pressure switch. The water-cooled condenser replaces the standard unit receiver.

Figure 3.5  Water-Cooled Condenser Section

Fig_condenser-section-water-cooled.jpg 

1.Sight Glass

2.Water-Cooled Condenser

3.Rupture Disc

4.Condenser Pressure Transducer

5.Quench Valve

6.Filter-Drier

7.Liquid Line Service Valve

8.Moisture/Liquid Indicator

9.Coupling (Water In)

10.Self Draining Coupling (Water Out)

11.Water Pressure Switch

- - - - -

3.1.7Control Box Section

The control box (Figure 3.6) includes the manual operation switches, circuit breaker (CB-1), compressor, fan and heater contactors, control power transformer, fuses, keypad, display module, current sensor module, controller module and the communications interface module.For units with three-phase evaporator fan motors, two additional contactors, PA & PB, are installed, see 2 & 3 below.

3.1.8Communications Interface Module

The communications interface module is a slave module which allows communication between the refrigeration unit and a ship system master central monitoring station. The module will respond to communication, and return information over the ships main power line. Refer to the master system technical manual for further information.

Figure 3.6  Control Box Section

fig-control-box-section.jpg 

1.Compressor Contactor

2.Evap Fan Contactor PA (3-Phase only)

3.Evap Fan Contactor PB (3-Phase only)

4.Heater Contactor

5.Display Module

6.Communications Interface Module

7.Controller/DataCORDER Module (Controller)

8.Key Pad

9.Emergency Defrost Light

10.Start-Stop Switch, ST

11.Remote Monitoring Receptacle

12.Manual Defrost Switch

13.Condenser Fan Switch

14.Controller Battery Pack

15.Interrogator Connector (Box Location)

16.Control Transformer

17.Evaporator Fan Contactor - E1

18.Evaporator Fan Contactor - S1

19.Evaporator Fan Contactor - S2 or EF

20.Evaporator Fan Contactor - E2 or ES

21.Condenser Fan Contactor

22.Circuit Breaker (CB1) - 460V

23.Current Sensor Module

- - - - -

3.2Refrigeration System Data

a. Compressor / Motor

Assembly

Number of Cylinders

6

Model

06DR

CFM

41

Weight (Dry)

118kg (260 lb)

Approved Oil

Castrol Icematic

Oil Charge degrees

3.6 liters (7.6 U.S. pints)

Oil Sight Glass

The oil level range, with the compressor off, should be between the bottom and one-eighth level of the sight glass.

b. Expansion Valve Super­heat

Verify at -18°C (0°F) con­tainer box temperature

4.5 to 6.7°C (8 to 12°F)

c. Heater Termination

Thermostat

Opens

54° (+/-3) C = 130° (+/-5) F

Closes

38° (+/-4) C = 100° (+/-7) F

d. High Pressure Switch

Cutout

25 (+/-1.0) kg/cm2 = 350 (+/-10) psig

Cut-In

18 (+/-0.7) kg/cm2 = 250 (+/-10) psig

EXPLOSION HAZARD: Failure to follow this WARNING can result in death, serious personal injury and / or property damage.
Never use air or gas mixtures containing oxygen (O2) for leak testing or operating the product.
Charge Only With R-134a: Refrigerant must conform to AHRI Standard 700 specification.

e. Refrigerant

R-134a

Conforming to AHRI standard 700 specifications.

f. Refrigerant Charge

Unit Configuration

Charge Requirements − R-134a

Water-Cooled Condenser

4.9kg (10.75 lbs)

Receiver

4kg (8.75 lbs)

NOTE:

When replacing components (g.), (h.) and (i.), refer to installation instructions included with replacement part.

g. Fusible Plug*

Melting point

99°C = (210°F)

Torque*

6.2 to 6.9mkg (45 to 50ft-lbs)

h. Sight Glass / Moisture

Indicator

Torque

8.9 to 9.7mkg (65 to 70ft-lbs)

i. Rupture Disc

Bursts at

35 +/- 5%kg/cm2 = (500 +/- 5%psig)

Torque (P/N 14-00215-03)

1.4 to 2mkg (10 to 15 ft-lbs)

j. Condenser Pressure

Transducer

Condenser Fan Starts

Condenser fan will start if condenser pressure is greater than 14.06kg/cm2 (200psig) OR the con­denser fan is OFF for more than 60 seconds.

Condenser Fan Stops

Condenser fan will stop if condenser pressure is less than 9.14kg/cm2 (130psig) AND the condenser fan remains ON for at least 30 seconds.

k. Unit Weight

Refer to unit model number plate.

l. Water Pressure Switch

Cut-In

0.5 +/-0.2kg/cm2 (7 +/-3psig)

Cutout

1.6 +/-0.4kg/cm2 (22 +/-5psig)

m. Discharge Pressure

Regulating Valve

Factory Setting

32.7 +/-2.5kg/cm2 (72 +/-5.5psig)

* Rupture Disc, part number 14-00215-04 may be installed as an alternate for the receiver mounted fusible plug.

3.3Electrical Data

a. Circuit Breaker

CB-1

Trips at 29 amps

CB-2 (50 amps)

Trips at 62.5amps

CB-2 (70 amp)

Trips at 87.5amps

b. Compressor Motor

Full Load Amps (FLA)

17.6amps @ 460VAC

(with current limiting set at 21 amps)

c. Condenser

Fan Motor

 

380 VAC, Single Phase,

50 Hz

460 VAC, Single Phase,

60 Hz

Full Load Amps

1.3 amps

1.6 amps

Horsepower

0.43 hp

0.75 hp

Rotations Per Minute

1425 rpm

1725 rpm

Voltage and Frequency

360 − 460 VAC +/- 2.5 Hz

400 − 500 VAC +/- 2.5 Hz

Bearing Lubrication

Factory lubricated, additional grease not required.

Rotation

Counter-clockwise when viewed from shaft end.

Single-Phase Evaporator Fan Motors

d. Evaporator

Fan Motor(s)

 

380 VAC/50 Hz

460 VAC/60 Hz

Full Load Amps High Speed

1.6

2.0

Full Load Amps Low Speed

0.8

1.0

Nominal Horsepower

High Speed

0.70

0.84

Nominal Horsepower

Low Speed

0.09

0.11

Rotations Per Minute

High Speed

2850 rpm

3450 rpm

Rotations Per Minute

Low Speed

1425 rpm

1725 rpm

Voltage and Frequency

360 − 460 VAC +/- 1.25 Hz

400 − 500 VAC +/- 1.5 Hz

Voltage & Frequency using power autotransformer

180 − 230VAC +/-1.25 Hz

200 − 250VAC +/-1.5 Hz

Bearing Lubrication

Factory lubricated, additional grease not required

Rotation

CW when viewed from shaft end

Three-Phase Evaporator Fan Motors

e. Evaporator

Fan Motor(s)

 

380 VAC/3 PH/50 Hz

460 VAC/3 PH/60 Hz

Full Load Amps High Speed

1.0

1.2

Full Load Amps Low Speed

0.6

0.6

Nominal Horsepower

High Speed

0.49

0.84

Nominal Horsepower

Low Speed

0.06

0.11

Rotations Per Minute

High Speed

2850 rpm

3450 rpm

Rotations Per Minute

Low Speed

1425 rpm

1725 rpm

Voltage and Frequency

360 − 460 VAC +/- 1.25 Hz

400 − 500 VAC +/- 1.5 Hz

Bearing Lubrication

Factory lubricated, additional grease not required

Rotation

CW when viewed from shaft end

f. Evaporator Coil

Heater

Number of Heaters

6

Rating

750 watts +5/-10% each @ 230 VAC

Resistance (cold)

66.8 to 77.2 ohms @ 20°C (68°F)

Type

Sheath

g. Fuses

Control Circuit

7.5 amps (F3A, F3B)

Controller/DataCORDER

5 amps (F1 & F2)

Emergency Defrost

5amps (FED)

Drain Line Heater

5 amps (FDH)

Humidity Power Transformer

5amps (FH)

h. Compressor Crankcase Heater

180watts @ 460VAC

i. Humidity Sensor

Orange wire

Power

Red wire

Output

Brown wire

Ground

Input voltage

5vdc

Output voltage

0 to 3.3vdc

Output voltage readings verses relative humidity (RH) percentage:

30%

0.99V

50%

1.65V

70%

2.31V

90%

2.97V

j. Controller

Setpoint Range

-30 to +30°C (-22 to +86°F)

3.4Safety and Protective Devices

Unit components are protected from damage by safety and protective devices listed in the following table. These devices monitor the unit operating conditions and open a set of electrical contacts when an unsafe condition occurs.

Table 3–1  Safety and Protective Devices

Unsafe Condition

Safety Device

Device Setting

Excessive current draw

Circuit Breaker (CB-1) − Manual Reset

Trips at 29 amps (460VAC)

Circuit Breaker (CB-2, 50 amp) − Manual Reset

Trips at 62.5 amps (230VAC)

Circuit Breaker (CB-2, 70 amp) − Manual Reset

Trips at 87.5 amps (230VAC)

Excessive current draw in control circuit

Fuse (F3A & F3B)

7.5 amp rating

Excessive current draw by controller

Fuse (F1 & F2)

5 amp rating

Excessive current draw by emergency defrost circuit

Fuse (FED)

5 amp rating

Excessive condenser fan motor winding temperature

Internal Protector (IP-CM) − Automatic Reset

N/A

Excessive compressor motor winding temperature

Internal Protector (IP-CP) − Automatic Reset

N/A

Excessive evaporator fan motor(s) winding temperature

Internal Protector(s) (IP-EM) − Automatic Reset

N/A

Abnormal pressures / temperatures in the high refrigerant side

Fusible Plug − Receiver

Rupture Disc − Water-Cooled Condenser

99°C = (210°F)

35kg/cm2 = (500psig)

Abnormally high discharge pressure

High Pressure Switch (HPS) − Automatic Reset

Open at 25kg/cm@ (350psig)

Close at 18kg/cm@ (250psig)

3.5Refrigeration Circuit

Starting at the compressor (see Figure 3.7, upper schematic), the suction gas is compressed to a higher pressure and temperature.

The gas flows through the discharge service valve into the pressure regulating valve. During periods of low ambi­ent operation, the discharge pressure regulating valve modulates the flow of refrigerant to maintain a pre-set mini­mum discharge pressure. Refrigerant gas then moves into the air-cooled condenser. When operating with the air-cooled condenser active, air flowing across the coil fins and tubes cools the gas to saturation temperature. By removing latent heat, the gas condenses to a high pressure/high temperature liquid and flows to the receiver, which stores the additional charge necessary for low temperature operation.

When operating with the water-cooled condenser active (see Figure 3.7, lower schematic), the refrigerant gas passes through the air-cooled condenser and enters the water-cooled condenser shell. The water flowing inside the tubing cools the gas to saturation temperature in the same manner as the air passing over the air-cooled con­denser. The refrigerant condenses on the outside of the tubes and exits as a high temperature liquid. The water-cooled condenser also acts as a receiver, storing excess refrigerant.

The liquid refrigerant continues through the liquid line service valve, the filter-drier (which keeps refrigerant clean and dry), and a heat exchanger (that increases sub-cooling of the liquid) to the thermostatic expansion valve (TXV).

As the liquid refrigerant passes through the variable orifice of the expansion valve, the pressure drops to suction pressure. In this process some of the liquid vaporizes to a gas (flash gas), removing heat from the remaining liquid. The liquid exits as a low pressure, low temperature, saturated mix. Heat is then absorbed from the return air by the balance of the liquid, causing it to vaporize in the evaporator coil. The vapor then flows through the suction tube back to the compressor.

The TXV is activated by the bulb strapped to the suction line near the evaporator outlet. The valve maintains a con­stant superheat at the coil outlet regardless of load conditions.

The TXV is a mechanical device that regulates the flow of liquid to the evaporator coil in order to maintain a rela­tively constant degree of superheat in the gas leaving the evaporator regardless of suction pressure.

The flow of liquid to the evaporator is regulated by a variable orifice which opens to increase refrigerant flow (decrease superheat), or closes to decrease refrigerant flow (increase superheat). The variable orifice is controlled by the temperature sensing bulb which is strapped to the suction line near the evaporator outlet.

During periods of low load, the suction modulating valve (SMV) decreases flow of refrigerant to the compressor. This action balances the compressor capacity with the load and prevents operation with low coil temperatures. In this mode of operation, the quench valve will open as required to provide sufficient liquid refrigerant flow into the suction line for cooling of the compressor motor. The quench valve senses refrigerant condition entering the com­pressor and modulates the flow to prevent entrance of liquid into the compressor.

The refrigeration system is also fitted with a condenser pressure transducer, which feeds information to the control­ler. When operating on the air-cooled condenser, the controller programming will operate the condenser fan so as to attempt to maintain discharge pressures above 130psig in low ambients. At ambients below 27°C (80°F), the condenser fan will cycle on and off depending on condenser pressure and operating times.

1.The condenser fan will start if the condenser pressure is greater than 200psig OR the condenser fan has been OFF for more than 60 seconds.

2.The condenser fan will stop if the condenser pressure is less than 130psig AND the condenser fan has been running for at least 30 seconds.

At ambients above 27°C (80°F), condenser pressure control is disabled and the condenser fan runs continuously.

On systems fitted with a water pressure switch, the condenser fan will be off when there is sufficient pressure to open the switch. If water pressure drops below the switch cut out setting, the condenser fan will be automatically started. When operating a system fitted with a condenser fan switch, the condenser fan will be off when the switch is placed in the “O” position. The condenser fan will be on when the switch is placed in the “I” position.

Figure 3.7  Refrigeration Circuit Schematic

Fig-Refrig-Circuit-Schematic.jpg