| |
(2)
Inspect the armature for short circuits
using a grower fixture. Place the armature in the growler
as shown in figure 4-6. Hold a thin strip of steel, such as
a hacksaw blade, about 1/32 inch from the armature.
While holding the steel strip in this position, rotate the
armature slowly in the growler. A short circuit will pull the
steel strip tightly against the armature core and cause
the strip to vibrate. If a short circuit is found, the
armature must be replaced.
Figure 4-6. Testing the armature for short circuits.
(3)
Inspect
the
armature
shaft
and
commutator for runout using a lathe or "V" blocks and a
dial indicator (fig. 4-7). If runout exists, the commutator
must be resurfaced until true.
Figure 4-7. Checking commutator runout.
(4)
Inspect the commutator contact surface.
A satisfactory condition is indicated by an even, highly
burnished, dark-copper color. If the contact surface is
rough, pitted, scored, burned, or coated with hard carbon
or oil, the commutator must be resurfaced. If the mica
insulation between the commutator bars is not 0.025 to
0.032 inch below the surface of the bars, it must be
undercut to the correct depth.
c.
Inspect the field coils for grounds by placing one
probe of a test lamp (fig. 4-8) on the field yoke and the
other probe on the field terminal. If the lamp lights, the
field coils are grounded and must be replaced if the
ground cannot be located and required.
Figure 4-8. Testing field coil for grounds.
4-5
|